Delta Rectiverter 1U 3kVA 48Vdc Power System
The Delta Rectiverter 1U is a combined rectifier and inverter shelf that supplies backed-up single-phase AC alongside 48Vdc from one 1U, 19in chassis. It is designed for sites where 230Vac or 115Vac loads need battery backup in parallel with the 48Vdc system. Built-in transfer technology switches the AC loads to battery power when the mains supp...
Read MoreThe Delta Rectiverter 1U is a combined rectifier and inverter shelf that supplies backed-up single-phase AC alongside 48Vdc from one 1U, 19in chassis. It is designed for sites where 230Vac or 115Vac loads need battery backup in parallel with the 48Vdc system. Built-in transfer technology switches the AC loads to battery power when the mains supply fails.
The shelf can be used in two ways. Integrated into a Delta DC system, it connects to the same Smartpack2, Smartpack S or Compack controller as the 48Vdc system and operates in parallel with Flatpack2 rectifiers. As a standalone system, it connects to any available 48Vdc source.
Output power is shared between the AC and DC ports, and both limits can be set to suit the attached load. AC load takes priority, so the DC power available depends on the AC demand at the time. Two front-mounted IEC 320-C13 sockets on 2-pole 10A distribution feed AC equipment directly from the shelf, and the modules are hot-pluggable.
Typical applications include power utilities, marine and offshore installations, railway and metro infrastructure, mobile and wireless telecom sites.
For a complete 48Vdc system, pair the Rectiverter 1U with Delta Flatpack2 HE rectifier modules and a Delta Smartpack2 Touch controller. Powerbox Australia provides local engineering support and system design assistance for Rectiverter projects.
Show Less
Features
- Supplies backed-up 230Vac or 115Vac and 48Vdc from one 1U shelf, for sites that need AC backup in parallel with the DC system
- Integrates into a Delta DC system on the same controller, or runs standalone from any available 48Vdc source
- Operates in parallel with Flatpack2 rectifiers and connects to Smartpack2, Smartpack S or Compack controllers via RJ45
- Built-in transfer technology switches AC loads to battery, with 5ms hold-up through voltage dips
- Adjustable AC and DC output limits match the shared output power to the attached load, with AC load given priority
- Two front-mounted IEC 320-C13 sockets on 2-pole 10A distribution feed AC equipment directly from the shelf
- Greater than 96% efficiency in mains mode and greater than 94% in inverter mode keeps conversion losses low
- Hot-pluggable modules with fuses in both line and neutral
- −40 to +55°C operating range for utility, marine, railway and telecom installations
Specifications
| AC Output Data | ||
|---|---|---|
| 4kW, 230Vac | 2kW, 115Vac | |
| Product number | PSPHT402RC301.1 | PSPHT202RC301.0 |
| Voltage (default) / (adjustable range) ¹⁾ | 230Vac / 200–240Vac | 115Vac / 100–127Vac |
| Frequency (default inverter mode) | 50Hz (adaptive) | 60Hz (adaptive) |
| Frequency (set-able inverter mode) | 50Hz, 60Hz or last synced 50/60Hz (adaptive) | 50Hz, 60Hz or last synced 50/60Hz (adaptive) |
| Power maximum (continuous / overload (<15s)) | 2400W (3000VA) / 4000VA | 1200W (1500VA) / 2000VA |
| Current maximum (continuous / overload (<15s)) | 13 ARMS / 17.4 ARMS | 13 ARMS / 17.4 ARMS |
| Current (maximum) Quick trip (20ms) | 64A (6 × nominal) | 64A (6 × nominal) |
| Hold up (voltage dips) (before switching to battery) | 5ms | 5ms |
| THD | <1.5% at resistive load | <1.5% at resistive load |
| Protection | Module: Fuse in L and N, Hot pluggable | Module: Fuse in L and N, Hot pluggable |
| DC Output Data | ||
|---|---|---|
| 4kW, 230Vac | 2kW, 115Vac | |
| Voltage (default) / (adjustable range) | 53.5Vdc / 43–58Vdc | 53.5Vdc / 43–58Vdc |
| Power (maximum @nominal input) ²⁾ | 2400W | 1200W |
| Current (maximum @nominal output Vdc) ²⁾ | 50A | 25A |
| Hold up time, maximum output power | >10ms; VOUT > 41Vdc | >10ms; VOUT > 41Vdc |
| Output features | Short circuit proof, Over voltage Shutdown, Bulk DC output connection to M6 bolt | Short circuit proof, Over voltage Shutdown, Bulk DC output connection to M6 bolt |
| Input Data | ||
|---|---|---|
| 4kW, 230Vac | 2kW, 115Vac | |
| AC Mains Input Voltage (range / LV disconnect) | 185–275Vac / 170Vac | 95–140Vac / 85Vac |
| AC Current (at nominal output voltage) ⁴⁾ | 14–24 ARMS | 14–24 ARMS |
| Frequency (default: sync range) | 47–53 & 57–63Hz | 57–63 & 47–53Hz |
| Frequency (set-able: sync range) | 47–53Hz, 57–63Hz or both (adaptive) | 47–53Hz, 57–63Hz or both (adaptive) |
| Power Factor / THD | >0.99 at 70% load or more / <3.5% | >0.99 at 70% load or more / <3.5% |
| DC Voltage nominal / extended range (no overload) ³⁾ | 45–58 / 40–45Vdc | 45–58 / 40–45Vdc |
| DC Current (maximum) | 64A / 90A during overload (15s) | 32A / 45A during overload (15s) |
| Input features | Module: Fuse in L and N, Hot pluggable, Varistor AC input individual screw terminals 6mm² for L, N & PE Bulk DC input connection to M6 bolt | Module: Fuse in L and N, Hot pluggable, Varistor AC input individual screw terminals 6mm² for L, N & PE Bulk DC input connection to M6 bolt |
| Other Specifications | |
|---|---|
| Controller support (RJ45) | Smartpack2, Smartpack S & Compack controllers |
| Efficiency | >96% (mains mode (AC/AC and AC/DC)), >94% (inverter mode (DC/AC)) |
| 2-pole AC distribution (connection IEC 320-C13 sockets) | 2pc, 10A, Output characteristics (optional 8A breaker with CS characteristics available) |
| Protection class | IP20 |
| Operating temperature | −40 to +55°C (−40 to +131°F), humidity 5–95% RH non-condensing |
| Storage temperature | −40 to +85°C (−40 to +185°F), humidity 0–99% RH non-condensing |
| Dimensions (W×D×H) / Weight | 482 × 395 × 44mm (1U) (19 × 17 × 1.8in) / 6kg (13lb) |
| Design Standards | |
|---|---|
| Electrical safety | EN IEC 62368-1:2020+A11:2020, EN 62040-1 UPS safety |
| EMC | ETSI EN 300 386 V.1.6.1, FCC CFR 47 Part 15 EN 61000-6-1/-2/-4/-5, EN 62040-2 (Cat C1 emissions, Cat C2/C3 immunity) |
| Environment | ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) Normal operating conditions as per IEC 62040-3:2011 clause 4.2 Other operating conditions as per IEC 62040-3:2011 clause 4.3, must be advised RoHS 3 (2015/863/EU) and WEEE (2008/98/EC) compliant |
| Notes | |
|---|---|
| 1) | Output voltage ranges configured in factory and have individual keying in top chassis |
| 2) | AC load has priority. Maximum available DC output power and current is dependent on instant AC load and AC input voltage; i.e. maximum 1600W at full AC power and nominal input for 230Vac |
| 3) | Reduced performance – no power boost and increased voltage THD on AC output |
| 4) | If DC port is overloaded pulling the voltage below 43V the input current may increase above this level |
Warranty & Returns
Warranty periods vary by product. Please refer to the Powerbox Warranty Policy for the applicable coverage period against manufacturing defects from date of purchase. For returns and RMA requests, please visit our RMA support page or contact our support team directly.