Battery Chargers and DC Power Systems

Delta DPR 3000B-110 3kW 110Vdc Rectifier Module

The Delta DPR 3000B-110 is a 3kW, 110Vdc hot-plug rectifier module and the power module in the Delta DPS 3000 110V DC power system. Each module converts a single-phase AC supply to 110Vdc, charging the station battery and supplying the load. Up to five modules fit in one shelf, for 15kW. The rectifier produces a regulated DC output for 110V and ...

Read More

The Delta DPR 3000B-110 is a 3kW, 110Vdc hot-plug rectifier module and the power module in the Delta DPS 3000 110V DC power system. Each module converts a single-phase AC supply to 110Vdc, charging the station battery and supplying the load. Up to five modules fit in one shelf, for 15kW.

The rectifier produces a regulated DC output for 110V and 125V nominal battery systems. The system controller sets and monitors each module over CAN bus, adjusting the output voltage for float, boost and equalise charging. In normal operation the rectifiers carry the standing load, and the battery takes over when AC is lost.

Modules in the same shelf share load within ±5% of maximum current. Three LEDs on the module front show its status at a glance, while detailed alarms and per-module data are reported to the Orion Touch controller over CAN bus.

Delta designed the DPR 3000B-110 for 110–125V battery systems in railway and metro, power utilities, and demanding industries such as marine, oil and gas, and process applications.

Adding capacity is a matter of fitting modules into empty slots in a DPS 3000 110V shelf, up to five for 15kW. The controller detects each new module and brings it into load sharing. One module more than the load needs gives N+1 redundancy: a 9kW load on four modules, for example, leaves 3kW spare. With a spare module on site, a failed unit can be swapped in minutes by hot-plugging, with no shutdown.

Need spares or more capacity? Tell us your system serial number or current module count and load, and our engineering team will confirm the module quantity for the capacity and redundancy you need.

Show Less

Model:
Unit Price
—
or send a quick enquiry about this product only
Delta DPR 3000B-110 3kW 110Vdc single-phase rectifier module, front angled view showing ventilation grille and status indicator LEDs.
Features
  • Lower energy and cooling costs: 96.5% peak efficiency means about 109W of loss per module at 3kW, or 545W across a full 15kW shelf
  • Minimal impact on the site AC supply: power factor above 0.99 and THD below 3.5% at full load keep harmonic load to a minimum
  • Tolerates low or variable AC supplies: 90–300Vac input, with derating at or below 176Vac, plus 90–400Vdc input capability
  • Headroom for hot equipment rooms and cabinets: rated −40 to +75°C, with derating above 50°C
  • No downtime for maintenance: hot-swappable from the front, so a module can be replaced without shutting the system down
  • Clean, stable DC for the load and battery: ripple of ≤500mVp-p and ≤100mVrms, with ±0.5% load regulation
  • Saves rack space: 3kW in an 84×41×265mm, 2.0kg module, a power density of 53.5W/in³, for up to 15kW per shelf
  • Better resilience to lightning-induced surges: input and output protection to EN 61000-4-5 on both the AC supply and DC output
  • No single module carries more than its share: modules in a shelf share load within ±5% of maximum current, set and monitored by the system controller over CAN bus
  • Simplifies compliance on rail and marine projects: railway EMC to EN 50121-4 and EN 50121-5, marine approval to EN 60945 and DNV-GL CG-0339
Specifications
Input
Voltage (nominal) 230Vac / 230Vdc
Voltage (range) 90–300Vac; derating ≤176Vac / 90–400Vdc; derating ≤176Vdc
Frequency 15–66Hz; derating ≤45Hz
Power factor >0.99
Total harmonic distortion <3.5% at full load
Lightning protection EN 61000-4-5
Output
Voltage (default)122.5Vdc
Voltage (adjustable range)89–171Vdc
Maximum output current24.5A
Maximum power at nominal input3,000W
Power density53.5W/in³
Peak efficiency96.5%
Load regulation±0.5%
Ripple≤500mVp-p / ≤100mVrms
Current sharing≤±5% of maximum current
Lightning protectionEN 61000-4-5
User Interface
Alarm and signallingCANbus to system controller
IndicationsGreen: Normal operation
Orange: Derating / current limit
Red: Protective shutdown / module failure
Mechanical
Dimensions (W×H×D)84×41×265mm (3.30×1.61×10.43in)
Weight2.0kg (4.4lb)
Environmental
Operating temperature−40 to +75°C (−40 to +167°F); derating above 50°C (+122°F)
Storage temperature−40 to +80°C (−40 to +176°F)
Altitude0–3,000m
Relative humidity0–95% RH, non-condensing
Acoustic noise≤58dBA
IP protectionIP20
CoolingFan
Standards
Safety TUV, CE, UL, UKCA
EMC EN IEC 61000-6-1/-2/-3/-4/-5
EN 55032 AC Class B & DC output Class A
Railway EN 50121-4, EN 50121-5
Marine EN 60945, DNV-GL CG-0339
Environment RoHS, WEEE
MTBF 100,000 hours at 25°C (+77°F)
Ordering Information
PMPDR302A0051-A DPR 3000B-110 ID:A1, 3,000W 110Vdc single-phase rectifier (single-packing)
Downloads
Delta-DPR-3000B-110-3kW-110V-DC-Rectifier-Datasheet.pdf
Warranty & Returns

Warranty periods vary by product. Please refer to the Powerbox Warranty Policy for the applicable coverage period against manufacturing defects from date of purchase. For returns and RMA requests, please visit our RMA support page or contact our support team directly.

FAQs
The Delta DPS 3000 110V DC power system. One shelf takes up to five modules, for 15kW.
Yes. Fit modules into empty slots, up to five per shelf, and the controller brings them into load sharing.
Yes. The DPR 3000B-110 is hot-pluggable from the front of the shelf.
The module itself is rated −40 to +75°C, with derating above 50°C. In a DPS 3000 110V shelf, the Orion Touch controller limits the system to 0 to +65°C.
110V and 125V nominal systems. The output is adjustable from 89–171Vdc, with a default of 122.5Vdc.
PMPDR302A0051-A, for spares and for adding capacity.
230Vac nominal, with a range of 90–300Vac (derating at or below 176Vac). It also accepts 90–400Vdc input.
Peak efficiency is 96.5%, with a power factor above 0.99 and total harmonic distortion below 3.5% at full load. At 3kW output, loss is about 109W per module.
Safety: TUV, CE, UL, UKCA. Railway EMC: EN 50121-4 and EN 50121-5. Marine: EN 60945 and DNV-GL CG-0339. General EMC: EN IEC 61000-6-1 to -5 and EN 55032. Environment: RoHS conformity, WEEE.