Lithium-Ion Batteries

Polarium SLB48-100-135-6 LFP Battery

The Polarium SLB48-100-135-6 is a compact, smart lithium battery built for mission-critical telecom and industrial power applications. Delivering 5120Wh of usable energy in a 3U 19" rackmount form factor, it leverages advanced Lithium Iron Phosphate (LFP) chemistry for exceptional safety, long cycle life, and thermal stability. Designed and manufactured to meet global standards, the battery features Polarium’s proprietary battery management system (BMS) with intelligent protections, automatic cell balancing, and secure remote monitoring. Native integration with leading DC power system controllers including Eltek ensures seamless deployment in hybrid, grid-connected, and off-grid applications.

View Models

Features

  • High energy density in compact footprint: 5120Wh capacity in a 3U 19” enclosure (440mm x 441mm x 132mm), weighing only 39.3 kg.
  • Advanced LFP chemistry: Delivers long cycle and calendar life, superior thermal stability, and inherently safer cell chemistry.
  • Smart BMS: Integrated battery management system ensures charge balancing, fault monitoring, and automatic protection against over-voltage, over-current, and temperature excursions.
  • Flexible communications: Supports RS485 and dual RJ45 ports with Modbus protocol for integration into remote monitoring systems.
  • Wide operating range: Supports charging from 0 to +55°C and discharging from -20 to +60°C.
  • High power performance: Capable of 6kW peak discharge for 60 seconds and up to 100A continuous discharge.
Specifications
TECHNICAL SPECIFICATIONS
Enclosure Size  19" 3U
Lithium chemistry  Iron Based (LFP)
Rated Voltage  48Vdc 
Rated Capacity Ah (0.2C, 25°C to 42 V)  100 Ah 
Rated Energy Wh (0.2C, 25°C to 42 V)  5120 Wh 
Calendar Life @ 80% SOC 20 years 
Peak Discharge Power  6kW for 60 seconds
Discharge Cutoff Current 100A, 300 seconds  
End-of-Discharge Voltage (LVBD)** 40Vdc
Charge Current Limitation (CLD)* 100A
Charge Voltage for 100% SOC 58.4 Vdc
Operating Temperature Charging 0 to +55°C (32 to 131°F)
Operating Temperature Discharging -20 to +60°C (-4 to 140°F)
Operating Relative Humidity  According to ETSI 300 019-1-3 class 3.2 (0-95%)
Storage Temperature  -20 to +60°C (-4 to 140°F)
Weight Approx. 39.3 Kg 
Dimensions mm (in") W 440 D 441 H 132 mm
(W 17.3” D 17.4” H 5.2”)
Circuit breaker 125A, BMS Controlled, Dual Pole
IP class  IP20
Communication Protocols RS485, RJ45 (2) ports, Modbus
Safety Standards IEC62619, IEC62368, UN38.3
Management & Monitoring  Software for PC (Studio). Included for full local monitoring and management. Remote connection via Modbus.

*Cut off when one cell reaches 2.5 V, 16 cells in series.
**If the charge current is 100 A or higher, the battery will automatically reduce the charge
current to 6-12 A temporarily.

Data subject to change without notice

Downloads
POLARIUM_SLB48-100-135-6_Gen.5_16S_PB.pdf
TECHNICAL SPECIFICATIONS
Enclosure Size  19" 3U
Lithium chemistry  Iron Based (LFP)
Rated Voltage  48Vdc 
Rated Capacity Ah (0.2C, 25°C to 42 V)  100 Ah 
Rated Energy Wh (0.2C, 25°C to 42 V)  5120 Wh 
Calendar Life @ 80% SOC 20 years 
Peak Discharge Power  6kW for 60 seconds
Discharge Cutoff Current 100A, 300 seconds  
End-of-Discharge Voltage (LVBD)** 40Vdc
Charge Current Limitation (CLD)* 100A
Charge Voltage for 100% SOC 58.4 Vdc
Operating Temperature Charging 0 to +55°C (32 to 131°F)
Operating Temperature Discharging -20 to +60°C (-4 to 140°F)
Operating Relative Humidity  According to ETSI 300 019-1-3 class 3.2 (0-95%)
Storage Temperature  -20 to +60°C (-4 to 140°F)
Weight Approx. 39.3 Kg 
Dimensions mm (in") W 440 D 441 H 132 mm
(W 17.3” D 17.4” H 5.2”)
Circuit breaker 125A, BMS Controlled, Dual Pole
IP class  IP20
Communication Protocols RS485, RJ45 (2) ports, Modbus
Safety Standards IEC62619, IEC62368, UN38.3
Management & Monitoring  Software for PC (Studio). Included for full local monitoring and management. Remote connection via Modbus.

*Cut off when one cell reaches 2.5 V, 16 cells in series.
**If the charge current is 100 A or higher, the battery will automatically reduce the charge
current to 6-12 A temporarily.

Data subject to change without notice

POLARIUM_SLB48-100-135-6_Gen.5_16S_PB.pdf

Find the Right Model

Model Number Rated Voltage (Vdc) Rated Capacity (Ah) Rated Energy (Wh)
product variant SLB48-100-135-6 48Vdc 100Ah 5120Wh

Need help finding the right product model?