Delta Electronics PMT2 100W Series Panel Mount AC/DC Power Supply
The Delta PMT2 100W Series is a range of high-reliability, low-profile panel mount power supplies designed for industrial control, automation, instrumentation, and information technology equipment where space efficiency, safety compliance, and long service life are essential. With a compact 30 mm low-profile enclosure and universal AC input (90–...
Read MoreThe Delta PMT2 100W Series is a range of high-reliability, low-profile panel mount power supplies designed for industrial control, automation, instrumentation, and information technology equipment where space efficiency, safety compliance, and long service life are essential.
With a compact 30 mm low-profile enclosure and universal AC input (90–264 Vac), the PMT2 100W Series integrates easily into space-constrained control panels and OEM equipment. Multiple single-output DC voltage options allow the series to support a wide variety of industrial and commercial applications.
Built for demanding environments, PMT2 100W power supplies operate from -30°C to +70°C with fanless convection cooling, reducing maintenance requirements and improving long-term reliability. Ultra-low no-load power consumption (<0.3 W) and high efficiency help minimise heat generation and energy loss inside electrical enclosures.
Certified to IEC/EN/UL 62368-1 and additional global safety and EMC standards, the PMT2 100W Series delivers dependable, compliant AC-DC power conversion. Backed by Powerbox local support, it provides a robust solution for modern industrial systems requiring reliable and long-life power.
Show Less
Features
- Universal AC Input: 90–264 Vac, 50/60 Hz
- Output Voltage Options: 12, 15, 24, 30, 36 and 48 Vdc
- Rated Output Current: Up to 8.5 A (model dependent)
- 100 W Single Output Panel Mount Power Supplies
- Wide Operating Temperature: -30°C to +70°C (-40°C cold start support)
- High Efficiency & Low Standby Power: <0.3 W no-load consumption
- Fanless Convection Cooling: Quiet, maintenance-free operation
- Adjustable Output Voltage: Supports voltage trimming and cable-drop compensation
- Industrial Protection Features: Overload, over-temperature, over-voltage and short-circuit protection
- Status Indication: Green DC OK LED
- Safety & EMC Compliance: IEC/EN/UL 62368-1, IEC 60335-1, IEC 61558-1/-2-16, AS/NZS CISPR 32
- High Reliability: MTBF >700,000 hours (Telcordia SR-332)
Specifications
| INPUT RATINGS/CHARACTERISTICS | ||||||
|---|---|---|---|---|---|---|
| Model Number | PMT-12V100W2BA | PMT-15V100W2BA | PMT-24V100W2BA |
PMT-30V100W2BA |
PMT-36V100W2BA | PMT-48V100W2BA |
| Nominal Input Voltage | 100...240 Vac | |||||
| Input Voltage Range | 90...264 Vac | |||||
| Nominal Input Frequency | 50...60 Hz | |||||
| Input Frequency Range | 47...63 Hz | |||||
| Input Current | 1.9 A typ. @ 115 Vac, 1.2 A typ. @ 230 Vac | |||||
| Efficiency at 100% Load @230Vac | 87.5% typ. | 88.0% typ. | 90.0% typ. | 90.0% typ. | 91.0% typ. | 91.5% typ. |
| No Load Power Consumption | < 0.3 W @ 230 Vac | |||||
| Max Inrush Current (Cold Start) | 55 A typ. @ 230 Vac | |||||
| Leakage Current | < 0.5 mA @ 240 Vac | |||||
| OUTPUT RATINGS/CHARACTERISTICS*² | ||||||
|---|---|---|---|---|---|---|
| Model Number | PMT-12V100W2BA | PMT-15V100W2BA | PMT-24V100W2BA | PMT-30V100W2BA | PMT-36V100W2BA | PMT-48V100W2BA |
| Nominal Output Voltage | 12 Vdc | 15 Vdc | 24 Vdc | 30 Vdc | 36 Vdc | 48 Vdc |
| Factory Set Point Tolerance | 12 Vdc ± 1% | 15 Vdc ± 1% | 24 Vdc ± 1% | 30 Vdc ± 1% | 36 Vdc ± 1% | 48 Vdc ± 1% |
| Output Voltage Adjustment Range | 10.8-13.2 Vdc | 13.5-16.5 Vdc | 21.6-26.4 Vdc | 27.0-33.0 Vdc | 32.4-39.6 Vdc | 43.2-52.8 Vdc |
| Output Current | 8.5 A | 7.0 A | 4.5 A | 3.6 A | 3.0 A | 2.3 A |
| Output Power | 102 W Max. | 105 W Max. | 108 W Max. | 108 W Max. | 108 W Max. | 110 W Max. |
| Line Regulation | ± 0.5% (@ 115 Vac & 230 Vac input) | |||||
| Load Regulation | ± 0.5% (@ 115 Vac & 230 Vac input) | |||||
| PARD*³ (20MHz) | < 120 mVpp @ 0°C to 70°C 360 mVpp typ. @ -30°C to 0°C |
< 150 mVpp @ 0°C to 70°C 450 mVpp typ. @ -30°C to 0°C |
< 200 mVpp @ 0°C to 70°C 600 mVpp typ. @ -30°C to 0°C |
|||
| Rise Time | 30 ms typ. @ 115 Vac & 230 Vac | |||||
| Start-up Time | 500 ms typ. @ 115 Vac & 230 Vac | |||||
| Hold-up Time | 9 ms typ. @ 115 Vac, 42 ms typ. @ 230 Vac | |||||
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 10% @ 115 & 230 Vac input, 10-100% load (Slew Rate: 2.5 A/μS, 50% duty cycle @ 5 Hz & 10 KHz) | |||||
| Start-up with Capacitive Loads | 8,000μF Max | 8,000μF Max | 8,000μF Max | 6,000μF Max | 3,000μF Max | 2,000μF Max |
| *2 For power de-rating from > 50°C to 70°C, see power de-rating on page 3. *3 PARD is measured with an AC coupling mode, and in parallel to end terminal with 0.1μF ceramic capacitor & 47μF electrolytic capacitor. PSU need to burn in > 5 minutes when AMB ≤ 0℃ |
||||||
| MECHANICAL | |||||||
|---|---|---|---|---|---|---|---|
| Model Number | PMT-12V100W2BA | PMT-15V100W2BA | PMT-24V100W2BA |
PMT-30V100W2BA |
PMT-36V100W2BA |
PMT-48V100W2BA |
|
| Case Chassis | Aluminum | ||||||
| Case Cover | SGCC | ||||||
| Dimensions (L x W x H) | 129 x 97 x 30 mm (5.08 x 3.82 x 1.18 inch) | ||||||
| Unit Weight | 0.285 kg (0.628 lb) | ||||||
| Indicator | Green LED (DC OK) | ||||||
| Cooling System | Convection | ||||||
| Terminal | M3.5 x 7 Pins (Rated 300 V / 20 A) | ||||||
| Wire | AWG 18-12 Current rating can refer to page 6 “Wire AWG Table” |
||||||
| Noise (1 Meter from power supply) | Sound Pressure Level (SPL) < 25 dBA | ||||||
| ENVIRONMENT | |||||||
|---|---|---|---|---|---|---|---|
| Model Number | PMT-12V100W2BA | PMT-15V100W2BA | PMT-24V100W2BA |
PMT-30V100W2BA |
PMT-36V100W2BA |
PMT-48V100W2BA | |
| Surrounding Air Temperature | Operating | -30°C to +70°C (-40°C Cold Start) | |||||
| Storage | -40°C to +85°C | ||||||
| Power De-rating | > 50°C de-rate power by 2% / °C < 115 Vac de-rate power by 0.6% / V (85% load @ 90 Vac) |
||||||
| Operating Humidity | 20 to 90% RH (Non-Condensing) | ||||||
| Operating Altitude | 0 to 5,000 Meters (0 to 16,400 ft) | ||||||
| Shock Test | Non- Operating | IEC 60068-2-27, Half Sine Wave: 50G for a duration of 11 ms, 3 shocks for each 3 directions | |||||
| Operating | IEC 60068-2-27, Half Sine Wave: 10G for a duration of 11 ms, 3 shock for each 3 directions. | ||||||
| Vibration | Non- Operating | IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09G); 20 min per axis for all X, Y, Z direction |
|||||
| Operating | IEC 60068-2-6, Sine Wave: 20Hz to 500 Hz (5G); 10 min per cycle, 60 min for each axis (X, Y, Z) |
||||||
| Over Voltage Category | II (Compliance to EN 62477-1 OVC III with 2000 meters altitude) | ||||||
| Pollution Degree | 3 | ||||||
| PROTECTIONS | ||||||
|---|---|---|---|---|---|---|
| Model Number | PMT-12V100W2BA | PMT-15V100W2BA | PMT-24V100W2BA |
PMT-30V100W2BA |
PMT-36V100W2BA |
PMT-48V100W2BA |
| Overvoltage |
13.2 V - 17.4 V SELV Output, Latch Mode |
16.5 V - 21.0 V SELV Output, Latch Mode |
26.4V - 33.6 V |
33.0 V - 40.5 V SELV Output, Latch Mode |
39.6 V - 48.6 V SELV Output, Latch Mode |
52.8 V - 64.8 V SELV Output, Latch Mode |
| Overload / Overcurrent | 110-175% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery) | |||||
| Over Temperature | Latch Mode | |||||
| Short Circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
|||||
| Protection Against Shock | Class I with PE*⁴ connection | |||||
| *4 PE: Primary Earth | ||||||
| RELIABILITY DATA | ||||||
|---|---|---|---|---|---|---|
| Model Number | PMT-12V100W2BA | PMT-15V100W2BA |
PMT-24V100W2BA |
PMT-30V100W2BA |
PMT-36V100W2BA |
PMT-48V100W2BA |
| MTBF | > 700,000 hrs as per Telcordia SR-332 I/P: 230 Vac, O/P: 100% Load, Ta: 25°C) |
|||||
| Expected Cap Life Time | 10 years (230 Vac, 50% load @ 40°C) | |||||
| SAFETY STANDARDS/DIRECTIVES | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Model Number | PMT-12V100W2BA | PMT-15V100W2BA | PMT-24V100W2BA | PMT-30V100W2BA | PMT-36V100W2BA | PMT-48V100W2BA | ||||||
| Safety Entry Low Voltage | SELV | |||||||||||
| Electrical Safety | TUV Bauart | EN 62368-1, EN 60335-1, EN 61558-1/-2-16 | ||||||||||
| cULus | UL 62368-1 and CAN/CSA C22.2 No. 62368-1 | |||||||||||
| CB scheme | IEC 62368-1, IEC 60950-1, IEC 60335-1, IEC 61558-1/-2-16 | |||||||||||
| KC | K 60950-1 | |||||||||||
| EAC | TP TC 004/2011 | |||||||||||
| BSMI | CNS 14336-1 | |||||||||||
| BIS | IS 13252 (Part 1) | |||||||||||
| CCC | GB 4943.1 | |||||||||||
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU | |||||||||||
| UKCA | In conformance with Electromagnetic Compatibility Regulations 2016 and Electrical Equipment (Safety) Regulations 2016 | |||||||||||
| Galvanic Isolation | Input to Output | 4.0 kVac | ||||||||||
| Input to Ground | 2.0 kVac | |||||||||||
| Output to Ground | 1.25 kVac | |||||||||||
| EMC | ||||
|---|---|---|---|---|
| Emissions (CE & RE) | CISPR 32, EN/BS EN 55032, EN/BS EN 61000-6-4, KN32, AS/NZS CISPR32 Compliance to EN/BS EN 55014-1, FCC Title 47, EN/BS EN 61000-6-3 : Class B | |||
| Immunity | EN/BS EN 55035, KN35, EN/BS EN 61000-6-2 Compliance to EN/BS EN 55014-2,EN/BS EN 61000-6-1 |
|||
| Electrostatic Discharge | IEC 61000-4-2 |
Level 4 Criteria A¹⁾ |
||
| Radiated Field | IEC 61000-4-3 |
Level 3 Criteria A¹⁾ |
||
| Electrical Fast Transient / Burst | IEC 61000-4-4 |
Level 3 Criteria A¹⁾ |
||
| Surge | IEC 61000-4-5 |
Level 4 Criteria A¹⁾ |
||
| Conducted | IEC 61000-4-6 | Level 3 Criteria A¹⁾ 150 kHz – 80 MHz, 10 Vrms |
||
| Power Frequency Magnetic Fields | IEC 61000-4-8 | Level 4 Criteria A¹⁾ 30 A/meter |
||
| Voltage Dips and Interruptions | IEC 61000-4-11 | 0% residual; 1 cycle, Criteria B 40% residual; 10 cycle, Criteria C³⁾ 70% residual; 25 cycle, Criteria C³⁾ |
||
| Harmonic Current Emission | IEC/EN/BS EN 61000-3-2 | Class A | ||
| Voltage Sag Immunity SEMI F47 – 0706 | 80% of 200 Vac 70% of 200 Vac 50% of 200 Vac |
160 Vac, 1000 ms 140 Vac, 500 ms 100 Vac, 200 ms |
Criteria A¹⁾ Criteria A¹⁾ Criteria A¹⁾ |
|
| 1) Criteria A: Normal performance within the specification limits 2) Criteria B: Output out of regulation, or shuts down during test. Automatically restored to normal operation after test. 3) Criteria C: Output out of regulation, shuts down during test (Need to recycle AC power cord to normal operation after test) 4) Asymmetrical: Common mode (Line to earth) 5) Symmetrical: Differential mode (Line to line) |
||||
Selection Table
| MODEL NUMBER | INPUT VOLTAGE RANGE | RATED OUTPUT VOLTAGE | RATED OUTPUT CURRENT |
|---|---|---|---|
| PMT-12V100W2BA |
90-264 Vac |
12Vdc | 8.5 A |
| PMT-15V100W2BA | 15Vdc | 7.0 A | |
| PMT-24V100W2BA | 24Vdc | 4.5 A | |
| PMT-30V100W2BA | 30Vdc | 3.6 A | |
| PMT-36V100W2BA | 36Vdc | 3.0 A | |
| PMT-48V100W2BA | 48Vdc | 2.3 A |
Technical Drawings
Warranty & Returns
Warranty periods vary by product. Please refer to the Powerbox Warranty Policy for the applicable coverage period against manufacturing defects from date of purchase. For returns and RMA requests, please visit our RMA support page or contact our support team directly.