AC/DC Power Supplies

Schaefer C4700A SERIES AC/DC Power Supply

The Schaefer C4700A Series is a high-performance AC/DC power supply for industrial applications, delivering output power of 1700W for PFC-enabled models and 2.5kW for non-PFC models. This series supports a wide range of DC output voltages from 5Vdc to 400Vdc. The C4700A Series is designed for natural convection cooling, ensuring reliable performance in various environments. Mounting options include chassis mount, wall mount, or 19" rack installation when used in conjunction with a separate 6U subrack. With options for monitoring, parallel/redundant operation, and conformal coating, the C4700A Series is ideal for use in demanding sectors such as Railway, Utilities, Mining, and Heavy Industry.

Features

  • Industrial Grade AC/DC Power Supply
  • Output Power: 1.7kW - 2.5kW
  • AC Input: 1-Phase and 3-Phase Models
  • Wide Range of DC outputs: 5, 9, 12, 15, 24, 28, 48, 60, 110, 220
  • Flexible mounting options via Chassis Mount, Wall or Euro Cassette (19" rackmount)
  • Natural Convection Cooling (increased airflow via external fan recommended for high power applications)
Specifications
INPUT
Input voltage 1ph 115/230Vac
3ph 200/400/480Vac
See selection table
Units will turn off with under or over input voltage.
No-load input power 3-6W model (series dependant)
Inrush current AC input limited by thermistor
Switch on time 1-2 seconds.
Input Options Option au: Autoranging for 115/230Vac input Option pr: Power OK via relay contacts
OUTPUT
Output voltage Voltage range; 4.5 - 400Vdc
See selection table
Output current See selection table.
Ripple & noise 1% + 30mVpp
Line regulation 0.1% (±10%)
Load regulation 0.2% typical, load step 10-90%
Load transient 6% typical, load step 10-90%
Response time 2-3ms typical ±1%
Temperature coefficient 0.02% per °C typical.
Holdup time 10mS at 220VAC typical
Turn on rise time 100mS typical (soft start)
Remote sensing Standard for all series
Efficiency 80%-92% typical
Output Options Option dd: Decoupling Diode for redundant / parallel operation
Option cs: Active Current Sharing
Option h: Remote on/off (inhibit)
Option dr: DC OK via relay contacts
PROTECTION
Overload protection Current limited at 105%–110% of full load.
Overvoltage protection OVP switches off module with automatic return to operation
Protection Options Option i: Inrush Current Limiting
Option sd: Reverse polarity protection for DC input by Series Diode
MTBF 100Khrs to 140Khrs at 40°C acc. to MIL-HDBK-217E (notice 1)
ENVIRONMENTAL
Operating temperature -20°C to +75°C
(optional -40 to 75C)
Load derating Derate 2.5% per °C, from +55°C to 75°C
Cooling H: Heatsink - natural convection
F: Fan - increased airflow recommended
TF: Temperature controlled Fan included See selection table
Environment Options Option c: Extended temperature range to -40°C
Storage temperature -40°C to +85°C
Humidity Up to 95% RH, non-condensing
STANDARDS
EMI standards acc. to EN61000-6-4 class A, optionally class B
Immunity standards acc. to EN61000-6-2
C-Tick AS/NZS CISPR11: 2002 Group1 Class A
Safety / Construction acc. to EN60950-1 / EN50178
Protection category IP20 acc. to EN60529
NEMA or others on request
MECHANICAL
Mounting See technical illustrations
Eurocassette, pluggable module for 19" subrack
Option w: Wall Mounting
Option cha: Chassis Mounting
Dimensions See Technical illustration
Connector H15 acc. to DIN 41612 H15 and high current connectors for I > 50A, or terminals / bolts / bars
Mechanical Options Option ms: Increased Mechanical Strength Option t: Tropical protection
19" Rack Mounting Options Subrack Height 3U, 5U, 6U
Wiring, Front Panels
Accessories: Fuses, MCBs, Mains on/off switch
Contact Powerbox for rack configuration
Selection Table
INPUT 100 -240VAC ± 10% WITH PFC OUTPUT AMPS INPUT 115VAC ± 20% INPUT 230VAC + 15% - 20% INPUT 115 ± 20% 230VAC + 15% - 20% INPUT 3X200VAC + 15% - 20% INPUT 3X400VAC + 15% - 20% INPUT 3X480VAC + 10% - 15% OUTPUT AMPS COOLING OUTPUT VOLTAGE VOLTAGE ADJUSTMENT
CP4790 180 C4760 C4780 C4790 C4760V C4780V C4790V 180 F 5 4.5-5.5
CP4791 150 C4761 C4781 C4791 C4761V C4781V C4791V 150 F 9 8-10
CP4792 120 C4762 C4782 C4792 C4762V C4782V C4792V 130 F 12 11-13
CP4793 100 C4763 C4783 C4793 C4763V C4783V C4793V 110 F 15 14-16
CP4794 70 C4764 C4784 C4794 C4764V C4784V C4794V 80 F 24 23-26
CP4795 60 C4765 C4785 C4795 C4765V C4785V C4795V 70 F 28 26-30
CP4799 35 C4769 C4789 C4799 C4769V C4789V C4799V 40 F 48 45-55
CP4796 25 C4766 C4786 C4796 C4766V C4786V C4796V 33 F 60 58-68
CP4797 14 C4767 C4787 C4797 C4767V C4787V C4797V 20 F 110 100-130
CP4797J 7 C4767J C4787J C4797J C4767VJ C4787VJ C4797VJ 10 F 200 190-200
Cooling H: Heatsink - natural convection
F: Fan - increased airflow recommended
TF: Temperature controlled Fan included
See selection table
Model configuration options: Add the options to the model number, eg. C4700-dd-dr-cs
Options for Input, Output, Environmental and Mechanical follow.
19" Rack Mounting Options Subrack Height 3U, 5U, 6U
Wiring, Front Panels
Accessories: Fuses, MCBs, Mains on/off switch
Contact Powerbox for rack configuration
INPUT OPTIONS
Option “i” (inrush current limiting): A thermistor is connected in series with the input lines which changes its resistance from high to low when it gets hot. It does not reduce the current surge if the input power is interrupted for a short period of time not allowing the thermistor to cool down. Thermistors are fitted as standard to all mains input models except for 1-phase input of models > 2.5kW. Thermistors are available up to 45A. For higher input current an electronic inrush current limitation can be offered.
Option “ie” electronic inrush current limiting An electronic circuit limits the inrush current.
Option “sd” (series diode): A series diode protects the module against input voltage of wrong polarity (additional power losses).
Option “ad” (anti-parallel diode): To avoid the power losses of a series diode a diode is provided with opposite polarity in parallel to the input blowing an internal or external fuse if the module is connected to a supply with wrong polarity.
Option “au” (auto-ranging) For standard dual AC input models the range of 115/230Vac is to be selected by connecting the input line to different pins on the connector. With auto-ranging the unit senses the input voltage and provides automatically the correct connection.
Option “p” (power fail): A signal (logic or relay) is given if the input voltage (AC or DC) drops below the specified limit. In AC input units we sense the rectified input voltage so that a power fail alarm will not be triggered if at light loads mains power returns before the input capacitors are substantially discharged.
Option “r” (relay): A relay instead of a logic signal is provided for failure indication.
output options
Option “dd” (decoupling diode): For redundant operation the outputs of two or more units are paralleled behind de-coupling diodes so that an internal fault of one module does not affect the operation of the others. These diodes cause power losses.
Option “cs” (active current sharing): An additional control circuit provides active current sharing via an interconnecting wire between converters that operate in parallel. Active current sharing should be used for multi-output units operating in parallel.
Option “csi” (current sharing interrupt): Option "csi" will effect the removal of the "cs" signal. Should there be an instance where a unit is not supplying the load, then the effect of its "cs" signal is removed, and the load voltage is unaffected by this condition.
Option “h1” (inhibit): A terminal connected to the negative input line also shuts off the converter. This can also be used in conjunction with a thermal trip which shuts the unit down.
Option “h2” (inhibit): Operation of the unit is inhibited if a voltage signal (5V/10mA) is applied in reference to the negative line of the (main) output.
Option “rco” (reducing current limiting at over temperature) A circuit reduces the current limiting level at higher temperature (to be specified).
Option “d” (DC-ok, one output): A logic signal is given if the output voltage (main output in multi-output systems) is below the specified limit.
Option “m” (DC-ok, all outputs): In multi-output systems a logic signal is provided if the voltage of any output is below the specified limit.
Option “ac” (AC ok) A logic signal connected to relay contacts is given if the output voltage of an inverter is below the specified limit.
Option "y" (sys-reset): This logic signal is a combination of power fail and DC-ok as specified for VME systems.
Option "r" (relay): A relay instead of a logic signal is provided for failure indication.
environmental options
Option "t" (tropical protection):The unit is given additional protection by a heavy coat of varnish on the printed circuit board(s) and components.
Option "c" (extended temperature range):The circuit is designed and tested for operation at an ambient temperature as low as –40 °C.
Option "ms" (increased mechanical strength): Screws are secured by Locktite and heavy components are fastened by ties and/or glue. Modules with the "ms" option meet the standard EN61373 regarding shock and vibration.
mechanical options
Standard mounting "Eurocassette" pluggable module for 19" sub-racks 8
Option "w" (wall mounting): Module is screwed against a mounting plate for installation in a cabinet. The load connections are typically a terminal block.
Option "cha" (chassis mount) Module is designed for installation to a structure or within cabinet. Screw type connectors are supplied with the module.
Option "din" (DIN rail mount) Module is designed for DIN rail mounting to a structure or within Cabinet. Screw type connectors are supplied with the module.
Technical Illustrations
Downloads
Schaefer_ccpbbp4700-AC-DC-PS-BatteryChargers-DC-DC-Converters.pdf
INPUT
Input voltage 1ph 115/230Vac
3ph 200/400/480Vac
See selection table
Units will turn off with under or over input voltage.
No-load input power 3-6W model (series dependant)
Inrush current AC input limited by thermistor
Switch on time 1-2 seconds.
Input Options Option au: Autoranging for 115/230Vac input Option pr: Power OK via relay contacts
OUTPUT
Output voltage Voltage range; 4.5 - 400Vdc
See selection table
Output current See selection table.
Ripple & noise 1% + 30mVpp
Line regulation 0.1% (±10%)
Load regulation 0.2% typical, load step 10-90%
Load transient 6% typical, load step 10-90%
Response time 2-3ms typical ±1%
Temperature coefficient 0.02% per °C typical.
Holdup time 10mS at 220VAC typical
Turn on rise time 100mS typical (soft start)
Remote sensing Standard for all series
Efficiency 80%-92% typical
Output Options Option dd: Decoupling Diode for redundant / parallel operation
Option cs: Active Current Sharing
Option h: Remote on/off (inhibit)
Option dr: DC OK via relay contacts
PROTECTION
Overload protection Current limited at 105%–110% of full load.
Overvoltage protection OVP switches off module with automatic return to operation
Protection Options Option i: Inrush Current Limiting
Option sd: Reverse polarity protection for DC input by Series Diode
MTBF 100Khrs to 140Khrs at 40°C acc. to MIL-HDBK-217E (notice 1)
ENVIRONMENTAL
Operating temperature -20°C to +75°C
(optional -40 to 75C)
Load derating Derate 2.5% per °C, from +55°C to 75°C
Cooling H: Heatsink - natural convection
F: Fan - increased airflow recommended
TF: Temperature controlled Fan included See selection table
Environment Options Option c: Extended temperature range to -40°C
Storage temperature -40°C to +85°C
Humidity Up to 95% RH, non-condensing
STANDARDS
EMI standards acc. to EN61000-6-4 class A, optionally class B
Immunity standards acc. to EN61000-6-2
C-Tick AS/NZS CISPR11: 2002 Group1 Class A
Safety / Construction acc. to EN60950-1 / EN50178
Protection category IP20 acc. to EN60529
NEMA or others on request
MECHANICAL
Mounting See technical illustrations
Eurocassette, pluggable module for 19" subrack
Option w: Wall Mounting
Option cha: Chassis Mounting
Dimensions See Technical illustration
Connector H15 acc. to DIN 41612 H15 and high current connectors for I > 50A, or terminals / bolts / bars
Mechanical Options Option ms: Increased Mechanical Strength Option t: Tropical protection
19" Rack Mounting Options Subrack Height 3U, 5U, 6U
Wiring, Front Panels
Accessories: Fuses, MCBs, Mains on/off switch
Contact Powerbox for rack configuration
INPUT 100 -240VAC ± 10% WITH PFC OUTPUT AMPS INPUT 115VAC ± 20% INPUT 230VAC + 15% - 20% INPUT 115 ± 20% 230VAC + 15% - 20% INPUT 3X200VAC + 15% - 20% INPUT 3X400VAC + 15% - 20% INPUT 3X480VAC + 10% - 15% OUTPUT AMPS COOLING OUTPUT VOLTAGE VOLTAGE ADJUSTMENT
CP4790 180 C4760 C4780 C4790 C4760V C4780V C4790V 180 F 5 4.5-5.5
CP4791 150 C4761 C4781 C4791 C4761V C4781V C4791V 150 F 9 8-10
CP4792 120 C4762 C4782 C4792 C4762V C4782V C4792V 130 F 12 11-13
CP4793 100 C4763 C4783 C4793 C4763V C4783V C4793V 110 F 15 14-16
CP4794 70 C4764 C4784 C4794 C4764V C4784V C4794V 80 F 24 23-26
CP4795 60 C4765 C4785 C4795 C4765V C4785V C4795V 70 F 28 26-30
CP4799 35 C4769 C4789 C4799 C4769V C4789V C4799V 40 F 48 45-55
CP4796 25 C4766 C4786 C4796 C4766V C4786V C4796V 33 F 60 58-68
CP4797 14 C4767 C4787 C4797 C4767V C4787V C4797V 20 F 110 100-130
CP4797J 7 C4767J C4787J C4797J C4767VJ C4787VJ C4797VJ 10 F 200 190-200
Cooling H: Heatsink - natural convection
F: Fan - increased airflow recommended
TF: Temperature controlled Fan included
See selection table
Model configuration options: Add the options to the model number, eg. C4700-dd-dr-cs
Options for Input, Output, Environmental and Mechanical follow.
19" Rack Mounting Options Subrack Height 3U, 5U, 6U
Wiring, Front Panels
Accessories: Fuses, MCBs, Mains on/off switch
Contact Powerbox for rack configuration
INPUT OPTIONS
Option “i” (inrush current limiting): A thermistor is connected in series with the input lines which changes its resistance from high to low when it gets hot. It does not reduce the current surge if the input power is interrupted for a short period of time not allowing the thermistor to cool down. Thermistors are fitted as standard to all mains input models except for 1-phase input of models > 2.5kW. Thermistors are available up to 45A. For higher input current an electronic inrush current limitation can be offered.
Option “ie” electronic inrush current limiting An electronic circuit limits the inrush current.
Option “sd” (series diode): A series diode protects the module against input voltage of wrong polarity (additional power losses).
Option “ad” (anti-parallel diode): To avoid the power losses of a series diode a diode is provided with opposite polarity in parallel to the input blowing an internal or external fuse if the module is connected to a supply with wrong polarity.
Option “au” (auto-ranging) For standard dual AC input models the range of 115/230Vac is to be selected by connecting the input line to different pins on the connector. With auto-ranging the unit senses the input voltage and provides automatically the correct connection.
Option “p” (power fail): A signal (logic or relay) is given if the input voltage (AC or DC) drops below the specified limit. In AC input units we sense the rectified input voltage so that a power fail alarm will not be triggered if at light loads mains power returns before the input capacitors are substantially discharged.
Option “r” (relay): A relay instead of a logic signal is provided for failure indication.
output options
Option “dd” (decoupling diode): For redundant operation the outputs of two or more units are paralleled behind de-coupling diodes so that an internal fault of one module does not affect the operation of the others. These diodes cause power losses.
Option “cs” (active current sharing): An additional control circuit provides active current sharing via an interconnecting wire between converters that operate in parallel. Active current sharing should be used for multi-output units operating in parallel.
Option “csi” (current sharing interrupt): Option "csi" will effect the removal of the "cs" signal. Should there be an instance where a unit is not supplying the load, then the effect of its "cs" signal is removed, and the load voltage is unaffected by this condition.
Option “h1” (inhibit): A terminal connected to the negative input line also shuts off the converter. This can also be used in conjunction with a thermal trip which shuts the unit down.
Option “h2” (inhibit): Operation of the unit is inhibited if a voltage signal (5V/10mA) is applied in reference to the negative line of the (main) output.
Option “rco” (reducing current limiting at over temperature) A circuit reduces the current limiting level at higher temperature (to be specified).
Option “d” (DC-ok, one output): A logic signal is given if the output voltage (main output in multi-output systems) is below the specified limit.
Option “m” (DC-ok, all outputs): In multi-output systems a logic signal is provided if the voltage of any output is below the specified limit.
Option “ac” (AC ok) A logic signal connected to relay contacts is given if the output voltage of an inverter is below the specified limit.
Option "y" (sys-reset): This logic signal is a combination of power fail and DC-ok as specified for VME systems.
Option "r" (relay): A relay instead of a logic signal is provided for failure indication.
environmental options
Option "t" (tropical protection):The unit is given additional protection by a heavy coat of varnish on the printed circuit board(s) and components.
Option "c" (extended temperature range):The circuit is designed and tested for operation at an ambient temperature as low as –40 °C.
Option "ms" (increased mechanical strength): Screws are secured by Locktite and heavy components are fastened by ties and/or glue. Modules with the "ms" option meet the standard EN61373 regarding shock and vibration.
mechanical options
Standard mounting "Eurocassette" pluggable module for 19" sub-racks 8
Option "w" (wall mounting): Module is screwed against a mounting plate for installation in a cabinet. The load connections are typically a terminal block.
Option "cha" (chassis mount) Module is designed for installation to a structure or within cabinet. Screw type connectors are supplied with the module.
Option "din" (DIN rail mount) Module is designed for DIN rail mounting to a structure or within Cabinet. Screw type connectors are supplied with the module.
Schaefer_ccpbbp4700-AC-DC-PS-BatteryChargers-DC-DC-Converters.pdf

Find the Right Model

Model Number Input Voltage (Vac) Output Voltage (Vdc) Output Current (A)
product variant CP4790 100...240Vac ± 10% 50/60Hz with PFC 5Vdc (Adj. 4.5 - 5.5Vdc) 180A
product variant CP4791 100...240Vac ± 10% 50/60Hz with PFC 9Vdc (Adj. 8 - 10Vdc) 150A
product variant CP4792 100...240Vac ± 10% 50/60Hz with PFC 12Vdc (Adj. 11 - 13Vdc) 120A
product variant CP4793 100...240Vac ± 10% 50/60Hz with PFC 15Vdc (Adj. 14 - 16Vdc) 100A
product variant CP4794 100...240Vac ± 10% 50/60Hz with PFC 24Vdc (Adj. 23 - 26Vdc) 70A
product variant CP4795 100...240Vac ± 10% 50/60Hz with PFC 28Vdc (Adj. 26 - 30Vdc) 60A
product variant CP4799 100...240Vac ± 10% 50/60Hz with PFC 48Vdc (Adj. 45 - 55Vdc) 35A
product variant CP4796 100...240Vac ± 10% 50/60Hz with PFC 60Vdc (Adj. 58 - 68Vdc) 25A
product variant CP4797 100...240Vac ± 10% 50/60Hz with PFC 110Vdc (Adj. 100 - 130Vdc) 14A
product variant CP4797J 100...240Vac ± 10% 50/60Hz with PFC 200Vdc(Adj. 190 - 200Vdc) 7A
product variant CP4798 100...240Vac ± 10% 50/60Hz with PFC 220Vdc (Adj. 200 - 250Vdc) 7A
product variant CP4798J 100...240Vac ± 10% 50/60Hz with PFC 400Vdc (Adj. 380 - 400Vdc) 3.5A
product variant C4760 115Vac ± 20 % 50/60Hz 5Vdc (Adj. 4.5 - 5.5Vdc) 180A
product variant C4761 115Vac ± 20 % 50/60Hz 9Vdc (Adj. 8 - 10Vdc) 150A
product variant C4762 115Vac ± 20 % 50/60Hz 12Vdc (Adj. 11 - 13Vdc) 130A
product variant C4763 115Vac ± 20 % 50/60Hz 15Vdc (Adj. 14 - 16Vdc) 110A
product variant C4764 115Vac ± 20 % 50/60Hz 24Vdc (Adj. 23 - 26Vdc) 80A
product variant C4765 115Vac ± 20 % 50/60Hz 28Vdc (Adj. 26 - 30Vdc) 70A
product variant C4769 115Vac ± 20 % 50/60Hz 48Vdc (Adj. 45 - 55Vdc) 40A
product variant C4766 115Vac ± 20 % 50/60Hz 60Vdc (Adj. 58 - 68Vdc) 33A
product variant C4767 115Vac ± 20 % 50/60Hz 110Vdc (Adj. 100 - 130Vdc) 20A
product variant C4767J 115Vac ± 20 % 50/60Hz 200Vdc(Adj. 190 - 200Vdc) 10A
product variant C4768 115Vac ± 20 % 50/60Hz 220Vdc (Adj. 200 - 250Vdc) 10A
product variant C4768J 115Vac ± 20 % 50/60Hz 400Vdc (Adj. 380 - 400Vdc) 5A
product variant C4780 230Vac +15%/-20% 50/60Hz 5Vdc (Adj. 4.5 - 5.5Vdc) 180A
product variant C4781 230Vac +15%/-20% 50/60Hz 9Vdc (Adj. 8 - 10Vdc) 150A
product variant C4782 230Vac +15%/-20% 50/60Hz 12Vdc (Adj. 11 - 13Vdc) 130A
product variant C4783 230Vac +15%/-20% 50/60Hz 15Vdc (Adj. 14 - 16Vdc) 110A
product variant C4784 230Vac +15%/-20% 50/60Hz 24Vdc (Adj. 23 - 26Vdc) 80A
product variant C4785 230Vac +15%/-20% 50/60Hz 28Vdc (Adj. 26 - 30Vdc) 70A
product variant C4789 230Vac +15%/-20% 50/60Hz 48Vdc (Adj. 45 - 55Vdc) 40A
product variant C4786 230Vac +15%/-20% 50/60Hz 60Vdc (Adj. 58 - 68Vdc) 33A
product variant C4787 230Vac +15%/-20% 50/60Hz 110Vdc (Adj. 100 - 130Vdc) 20A
product variant C4787J 230Vac +15%/-20% 50/60Hz 200Vdc(Adj. 190 - 200Vdc) 10A
product variant C4788 230Vac +15%/-20% 50/60Hz 220Vdc (Adj. 200 - 250Vdc) 10A
product variant C4788J 230Vac +15%/-20% 50/60Hz 400Vdc (Adj. 380 - 400Vdc) 5A
product variant C4790 115Vac ± 20 % 50/60Hz or 230Vac +15%/-20% 50/60Hz 5Vdc (Adj. 4.5 - 5.5Vdc) 180A
product variant C4791 115Vac ± 20 % 50/60Hz or 230Vac +15%/-20% 50/60Hz 9Vdc (Adj. 8 - 10Vdc) 150A
product variant C4792 115Vac ± 20 % 50/60Hz or 230Vac +15%/-20% 50/60Hz 12Vdc (Adj. 11 - 13Vdc) 130A
product variant C4793 115Vac ± 20 % 50/60Hz or 230Vac +15%/-20% 50/60Hz 15Vdc (Adj. 14 - 16Vdc) 110A
product variant C4794 115Vac ± 20 % 50/60Hz or 230Vac +15%/-20% 50/60Hz 24Vdc (Adj. 23 - 26Vdc) 80A
product variant C4795 115Vac ± 20 % 50/60Hz or 230Vac +15%/-20% 50/60Hz 28Vdc (Adj. 26 - 30Vdc) 70A
product variant C4799 115Vac ± 20 % 50/60Hz or 230Vac +15%/-20% 50/60Hz 48Vdc (Adj. 45 - 55Vdc) 40A
product variant C4796 115Vac ± 20 % 50/60Hz or 230Vac +15%/-20% 50/60Hz 60Vdc (Adj. 58 - 68Vdc) 33A
product variant C4797 115Vac ± 20 % 50/60Hz or 230Vac +15%/-20% 50/60Hz 110Vdc (Adj. 100 - 130Vdc) 20A
product variant C4797J 115Vac ± 20 % 50/60Hz or 230Vac +15%/-20% 50/60Hz 200Vdc(Adj. 190 - 200Vdc) 10A
product variant C4798 115Vac ± 20 % 50/60Hz or 230Vac +15%/-20% 50/60Hz 220Vdc (Adj. 200 - 250Vdc) 10A
product variant C4798J 115Vac ± 20 % 50/60Hz or 230Vac +15%/-20% 50/60Hz 400Vdc (Adj. 380 - 400Vdc) 5A
product variant C4760V 3 x 200Vac +15%/-20% 50/60Hz 5Vdc (Adj. 4.5 - 5.5Vdc) 180A
product variant C4761V 3 x 200Vac +15%/-20% 50/60Hz 9Vdc (Adj. 8 - 10Vdc) 150A
product variant C4762V 3 x 200Vac +15%/-20% 50/60Hz 12Vdc (Adj. 11 - 13Vdc) 130A
product variant C4763V 3 x 200Vac +15%/-20% 50/60Hz 15Vdc (Adj. 14 - 16Vdc) 110A
product variant C4764V 3 x 200Vac +15%/-20% 50/60Hz 24Vdc (Adj. 23 - 26Vdc) 80A
product variant C4765V 3 x 200Vac +15%/-20% 50/60Hz 28Vdc (Adj. 26 - 30Vdc) 70A
product variant C4769V 3 x 200Vac +15%/-20% 50/60Hz 48Vdc (Adj. 45 - 55Vdc) 40A
product variant C4766V 3 x 200Vac +15%/-20% 50/60Hz 60Vdc (Adj. 58 - 68Vdc) 33A
product variant C4767V 3 x 200Vac +15%/-20% 50/60Hz 110Vdc (Adj. 100 - 130Vdc) 20A
product variant C4767VJ 3 x 200Vac +15%/-20% 50/60Hz 200Vdc(Adj. 190 - 200Vdc) 10A
product variant C4768V 3 x 200Vac +15%/-20% 50/60Hz 220Vdc (Adj. 200 - 250Vdc) 10A
product variant C4768VJ 3 x 200Vac +15%/-20% 50/60Hz 400Vdc (Adj. 380 - 400Vdc) 5A
product variant C4780V 3 x 400Vac +15%/-20% 50/60Hz 5Vdc (Adj. 4.5 - 5.5Vdc) 180A
product variant C4781V 3 x 400Vac +15%/-20% 50/60Hz 9Vdc (Adj. 8 - 10Vdc) 150A
product variant C4782V 3 x 400Vac +15%/-20% 50/60Hz 12Vdc (Adj. 11 - 13Vdc) 130A
product variant C4783V 3 x 400Vac +15%/-20% 50/60Hz 15Vdc (Adj. 14 - 16Vdc) 110A
product variant C4784V 3 x 400Vac +15%/-20% 50/60Hz 24Vdc (Adj. 23 - 26Vdc) 80A
product variant C4785V 3 x 400Vac +15%/-20% 50/60Hz 28Vdc (Adj. 26 - 30Vdc) 70A
product variant C4789V 3 x 400Vac +15%/-20% 50/60Hz 48Vdc (Adj. 45 - 55Vdc) 40A
product variant C4786V 3 x 400Vac +15%/-20% 50/60Hz 60Vdc (Adj. 58 - 68Vdc) 33A
product variant C4787V 3 x 400Vac +15%/-20% 50/60Hz 110Vdc (Adj. 100 - 130Vdc) 20A
product variant C4787VJ 3 x 400Vac +15%/-20% 50/60Hz 200Vdc(Adj. 190 - 200Vdc) 10A
product variant C4788V 3 x 400Vac +15%/-20% 50/60Hz 220Vdc (Adj. 200 - 250Vdc) 10A
product variant C4788VJ 3 x 400Vac +15%/-20% 50/60Hz 400Vdc (Adj. 380 - 400Vdc) 5A
product variant C4790V 3 x 480Vac +10%/-15% 50/60Hz 5Vdc (Adj. 4.5 - 5.5Vdc) 180A
product variant C4791V 3 x 480Vac +10%/-15% 50/60Hz 9Vdc (Adj. 8 - 10Vdc) 150A
product variant C4792V 3 x 480Vac +10%/-15% 50/60Hz 12Vdc (Adj. 11 - 13Vdc) 130A
product variant C4793V 3 x 480Vac +10%/-15% 50/60Hz 15Vdc (Adj. 14 - 16Vdc) 110A
product variant C4794V 3 x 480Vac +10%/-15% 50/60Hz 24Vdc (Adj. 23 - 26Vdc) 80A
product variant C4795V 3 x 480Vac +10%/-15% 50/60Hz 28Vdc (Adj. 26 - 30Vdc) 70A
product variant C4799V 3 x 480Vac +10%/-15% 50/60Hz 48Vdc (Adj. 45 - 55Vdc) 40A
product variant C4796V 3 x 480Vac +10%/-15% 50/60Hz 60Vdc (Adj. 58 - 68Vdc) 33A
product variant C4797V 3 x 480Vac +10%/-15% 50/60Hz 110Vdc (Adj. 100 - 130Vdc) 20A
product variant C4797VJ 3 x 480Vac +10%/-15% 50/60Hz 200Vdc(Adj. 190 - 200Vdc) 10A
product variant C4798V 3 x 480Vac +10%/-15% 50/60Hz 220Vdc (Adj. 200 - 250Vdc) 10A
product variant C4798VJ 3 x 480Vac +10%/-15% 50/60Hz 400Vdc (Adj. 380 - 400Vdc) 5A