DC/DC Converters

Schaefer C3500D SERIES DC/DC Converter

The Schaefer C3500D Series Industrial Grade DC/DC Converter is a reliable and efficient power solution designed for demanding industrial environments. Delivering power outputs between 700W and 850W, the C3500D supports DC input voltages from 18Vdc to 640Vdc and offers output voltages ranging from 5Vdc to 400Vdc in both step-up and step-down configurations. Its flexibility allows for stand-alone use or integration into parallel-connected systems for larger or redundant applications. With natural convection cooling, active cooling is required only for 5Vdc output versions. Flexible mounting options include wall mount, chassis mount, or 19" rackmount via a separate 6U subrack. Optional features such as monitoring, control, and enhanced environmental protection enhance adaptability and durability. Suitable for applications in railway, power utilities (generation, transmission, and distribution), renewable energy, and mining industries, the C3500D provides dependable performance where reliability is essential.

Features

  • Power Rating: 700W to 850W.
  • DC Input/Output: Input range 18Vdc to 640Vdc; output range 5Vdc to 400Vdc.
  • Cooling: Natural convection; active cooling for 5Vdc output models only.
  • Mounting: Wall mount, chassis mount, or 19" rackmount via a 6U subrack.
  • Optional Features: Monitoring, control, mechanical strength, and enhanced environmental protection.
  • Applications: Railway, Power Utilities (Generation, Transmission, and Distribution), Renewable Energy, and Mining industries.
Specifications
INPUT
Input voltage DC Input voltage: 10 - 800Vdc
See selection table
Units will turn off with under or over input voltage.
No-load input power 5-6W model (series dependent)
Switch on time 1-2 seconds.
OUTPUT
Output voltage Voltage range; 4.5 - 400Vdc See selection table
Output current See selection table.
Ripple & noise 1% + 30mVpp
Line regulation 0.1% (±10%)
Load regulation 0.2% typical, load step 10-90%
Load transient 6% typical, load step 10-90%
Response time 2-3ms typical ±1%
Temperature coefficient 0.02% per °C typical.
Holdup time 10mS at 220VAC typical
Turn on rise time 100mS typical (soft start)
Remote sensing Standard for all series
Efficiency 80%-92% typical
Output Options Option dd: Decoupling Diode for redundant / parallel operation
Option cs: Active Current Sharing
Option h: Remote on/off (inhibit)
Option dr: DC OK via relay contacts
PROTECTION
Overload protection Current limited at 105%–110% of full load.
Overvoltage protection OVP switches off module with automatic return to operation
Protection Options Option i: Inrush Current Limiting for DC input
Option sd: Reverse polarity protection for DC input by Series Diode
MTBF 100Khrs to 140Khrs at 40°C acc. to MIL-HDBK-217E (notice 1)
ENVIRONMENTAL
Operating temperature -20°C to +75°C (optional -40 to 75C)
Load derating Derate 2.5% per °C, from +55°C to 75°C
Cooling H: Heatsink - natural convection
F: Fan - increased airflow recommended
TF: Temperature controlled Fan included
See selection table
Environment Options Option c: Extended temperature range to -40°C
Storage temperature -40°C to +85°C
Humidity Up to 95% RH, non-condensing
STANDARDS
EMI standards acc. to EN61000-6-4 class A, optionally class B
Immunity standards acc. to EN61000-6-2
C-Tick AS/NZS CISPR11: 2002 Group1 Class A
Safety / Construction acc. to EN60950-1 / EN50178
Protection category IP20 acc. to EN60529 NEMA or others on request
MECHANICAL
Mounting See technical illustrations
Eurocassette, pluggable module for 19" subrack
Option w: Wall Mounting
Option cha: Chassis Mounting
Dimensions See Technical illustration
Connector H15 acc. to DIN 41612 H15 and high current connectors for I > 50A, or terminals / bolts / bars
Mechanical Options Option ms: Increased Mechanical Strength
Option t: Tropical protection
19" Rack Mounting Options Subrack Height 3U, 5U, 6U
Wiring, Front Panels
Accessories: Fuses, MCBs, Mains on/off switch
Contact Powerbox for rack configuration
Selection Table
INPUT 18-36V OUTPUT AMPS INPUT 36-75V INPUT 45-90V INPUT 80-160V INPUT 160 – 320V INPUT 320 – 380V INPUT 320 – 640V OUTPUT AMPS COOLING OUTPUT VDC OUTPUT RANGE
C3520 80 C3530 C3540 C3550 C3570 C3580Z C3570G 100 F 5 4.5 – 5.5
C3521 55 C3531 C3541 C3551 C3571 C3581Z C3571G 65 H 9 8 – 10
C3522 50 C3532 C3542 C3552 C3572 C3582Z C3572G 56 H 12 11 – 13
C3523 40 C3533 C3543 C3553 C3573 C3583Z C3573G 45 H 15 14 – 16
C3524 27 C3534 C3544 C3554 C3574 C3584Z C3574G 30 H 24 23 – 26
C3525 23 C3535 C3545 C3555 C3575 C3585Z C3575G 27 H 28 26 – 30
C3529 12 C3539 C3549 C3559 C3579 C3589Z C3579G 14 H 48 45 – 55
C3526 10 C3536 C3546 C3556 C3576 C3586Z C3576G 12 H 60 58 – 68
C3527 5.3 C3537 C3547 C3557 C3577 C3587Z C3577G 6.5 H 110 100 – 130
C3527J 3.5 C3537J C3547J C 3557J C3577J C3587ZJ C3577GJ 4 H 200 190 – 200
C3528 2.8 C3538 C3548 C3558 C3578 C3588Z C3578G 3.5 H 220 200 – 250
C3528J 1.7 C3538J C3548J C3558J C3578J C3588ZJ C3578GJ 2 H 400 380 – 400
Cooling
H: Heatsink - natural convection
F: Fan - increased airflow recommended
TF: Temperature controlled Fan included
See selection table
Model designation options: Add the designation of options to the model number, eg. C3520-dd-dr-cs Options for Input, Output, Environmental and Mechanical follow.
19" Rack Mounting Options Subrack Height 3U, 5U, 6U Wiring, Front Panels Accessories: Fuses, MCBs, Mains on/off switch Contact Powerbox for rack configuration
INPUT OPTIONS
Option “i” (inrush current limiting): A thermistor is connected in series with the input lines which changes its resistance from high to low when it gets hot. It does not reduce the current surge if the input power is interrupted for a short period of time not allowing the thermistor to cool down. Thermistors are fitted as standard to all mains input models except for 1-phase input of models > 2.5kW. Thermistors are available up to 45A. For higher input current an electronic inrush current limitation can be offered.
Option “ie” electronic inrush current limiting An electronic circuit limits the inrush current.
Option “sd” (series diode): A series diode protects the module against input voltage of wrong polarity (additional power losses).
Option “ad” (anti-parallel diode): To avoid the power losses of a series diode a diode is provided with opposite polarity in parallel to the input blowing an internal or external fuse if the module is connected to a supply with wrong polarity.
Option “au” (auto-ranging) For standard dual AC input models the range of 115/230Vac is to be selected by connecting the input line to different pins on the connector. With auto-ranging the unit senses the input voltage and provides automatically the correct connection.
Option “p” (power fail): A signal (logic or relay) is given if the input voltage (AC or DC) drops below the specified limit. In AC input units we sense the rectified input voltage so that a power fail alarm will not be triggered if at light loads mains power returns before the input capacitors are substantially discharged.
Option “r” (relay): A relay instead of a logic signal is provided for failure indication.
output options
Option “dd” (decoupling diode): For redundant operation the outputs of two or more units are paralleled behind de-coupling diodes so that an internal fault of one module does not affect the operation of the others. These diodes cause power losses.
Option “cs” (active current sharing): An additional control circuit provides active current sharing via an interconnecting wire between converters that operate in parallel. Active current sharing should be used for multi-output units operating in parallel.
Option “csi” (current sharing interrupt): Option "csi" will effect the removal of the "cs" signal. Should there be an instance where a unit is not supplying the load, then the effect of its "cs" signal is removed, and the load voltage is unaffected by this condition.
Option “h1” (inhibit): A terminal connected to the negative input line also shuts off the converter. This can also be used in conjunction with a thermal trip which shuts the unit down.
Option “h2” (inhibit): Operation of the unit is inhibited if a voltage signal (5V/10mA) is applied in reference to the negative line of the (main) output.
Option “rco” (reducing current limiting at over temperature) A circuit reduces the current limiting level at higher temperature (to be specified).
Option “d” (DC-ok, one output): A logic signal is given if the output voltage (main output in multi-output systems) is below the specified limit.
Option “m” (DC-ok, all outputs): In multi-output systems a logic signal is provided if the voltage of any output is below the specified limit.
Option “ac” (AC ok) A logic signal connected to relay contacts is given if the output voltage of an inverter is below the specified limit.
Option "y" (sys-reset): This logic signal is a combination of power fail and DC-ok as specified for VME systems.
Option "r" (relay): A relay instead of a logic signal is provided for failure indication.
environment options
Option "t" (tropical protection):The unit is given additional protection by a heavy coat of varnish on the printed circuit board(s) and components.
Option "c" (extended temperature range):The circuit is designed and tested for operation at an ambient temperature as low as –40 °C.
Option "ms" (increased mechanical strength): Screws are secured by Locktite and heavy components are fastened by ties and/or glue. Modules with the "ms" option meet the standard EN61373 regarding shock and vibration.
mechanical options
Standard mounting "Eurocassette" pluggable module for 19" sub-racks 8
Option "w" (wall mounting): Module is screwed against a mounting plate for installation in a cabinet. The load connections are typically a terminal block.
Option "cha" (chassis mount) Module is designed for installation to a structure or within cabinet. Screw type connectors are supplied with the module.
Option "din" (DIN rail mount) Module is designed for DIN rail mounting to a structure or within Cabinet. Screw type connectors are supplied with the module.
Technical Illustrations
Downloads
Schaefer_cb3500-AC-DC-PS-BatteryChargers-DC-DC-Converters.pdf
INPUT
Input voltage DC Input voltage: 10 - 800Vdc
See selection table
Units will turn off with under or over input voltage.
No-load input power 5-6W model (series dependent)
Switch on time 1-2 seconds.
OUTPUT
Output voltage Voltage range; 4.5 - 400Vdc See selection table
Output current See selection table.
Ripple & noise 1% + 30mVpp
Line regulation 0.1% (±10%)
Load regulation 0.2% typical, load step 10-90%
Load transient 6% typical, load step 10-90%
Response time 2-3ms typical ±1%
Temperature coefficient 0.02% per °C typical.
Holdup time 10mS at 220VAC typical
Turn on rise time 100mS typical (soft start)
Remote sensing Standard for all series
Efficiency 80%-92% typical
Output Options Option dd: Decoupling Diode for redundant / parallel operation
Option cs: Active Current Sharing
Option h: Remote on/off (inhibit)
Option dr: DC OK via relay contacts
PROTECTION
Overload protection Current limited at 105%–110% of full load.
Overvoltage protection OVP switches off module with automatic return to operation
Protection Options Option i: Inrush Current Limiting for DC input
Option sd: Reverse polarity protection for DC input by Series Diode
MTBF 100Khrs to 140Khrs at 40°C acc. to MIL-HDBK-217E (notice 1)
ENVIRONMENTAL
Operating temperature -20°C to +75°C (optional -40 to 75C)
Load derating Derate 2.5% per °C, from +55°C to 75°C
Cooling H: Heatsink - natural convection
F: Fan - increased airflow recommended
TF: Temperature controlled Fan included
See selection table
Environment Options Option c: Extended temperature range to -40°C
Storage temperature -40°C to +85°C
Humidity Up to 95% RH, non-condensing
STANDARDS
EMI standards acc. to EN61000-6-4 class A, optionally class B
Immunity standards acc. to EN61000-6-2
C-Tick AS/NZS CISPR11: 2002 Group1 Class A
Safety / Construction acc. to EN60950-1 / EN50178
Protection category IP20 acc. to EN60529 NEMA or others on request
MECHANICAL
Mounting See technical illustrations
Eurocassette, pluggable module for 19" subrack
Option w: Wall Mounting
Option cha: Chassis Mounting
Dimensions See Technical illustration
Connector H15 acc. to DIN 41612 H15 and high current connectors for I > 50A, or terminals / bolts / bars
Mechanical Options Option ms: Increased Mechanical Strength
Option t: Tropical protection
19" Rack Mounting Options Subrack Height 3U, 5U, 6U
Wiring, Front Panels
Accessories: Fuses, MCBs, Mains on/off switch
Contact Powerbox for rack configuration
INPUT 18-36V OUTPUT AMPS INPUT 36-75V INPUT 45-90V INPUT 80-160V INPUT 160 – 320V INPUT 320 – 380V INPUT 320 – 640V OUTPUT AMPS COOLING OUTPUT VDC OUTPUT RANGE
C3520 80 C3530 C3540 C3550 C3570 C3580Z C3570G 100 F 5 4.5 – 5.5
C3521 55 C3531 C3541 C3551 C3571 C3581Z C3571G 65 H 9 8 – 10
C3522 50 C3532 C3542 C3552 C3572 C3582Z C3572G 56 H 12 11 – 13
C3523 40 C3533 C3543 C3553 C3573 C3583Z C3573G 45 H 15 14 – 16
C3524 27 C3534 C3544 C3554 C3574 C3584Z C3574G 30 H 24 23 – 26
C3525 23 C3535 C3545 C3555 C3575 C3585Z C3575G 27 H 28 26 – 30
C3529 12 C3539 C3549 C3559 C3579 C3589Z C3579G 14 H 48 45 – 55
C3526 10 C3536 C3546 C3556 C3576 C3586Z C3576G 12 H 60 58 – 68
C3527 5.3 C3537 C3547 C3557 C3577 C3587Z C3577G 6.5 H 110 100 – 130
C3527J 3.5 C3537J C3547J C 3557J C3577J C3587ZJ C3577GJ 4 H 200 190 – 200
C3528 2.8 C3538 C3548 C3558 C3578 C3588Z C3578G 3.5 H 220 200 – 250
C3528J 1.7 C3538J C3548J C3558J C3578J C3588ZJ C3578GJ 2 H 400 380 – 400
Cooling
H: Heatsink - natural convection
F: Fan - increased airflow recommended
TF: Temperature controlled Fan included
See selection table
Model designation options: Add the designation of options to the model number, eg. C3520-dd-dr-cs Options for Input, Output, Environmental and Mechanical follow.
19" Rack Mounting Options Subrack Height 3U, 5U, 6U Wiring, Front Panels Accessories: Fuses, MCBs, Mains on/off switch Contact Powerbox for rack configuration
INPUT OPTIONS
Option “i” (inrush current limiting): A thermistor is connected in series with the input lines which changes its resistance from high to low when it gets hot. It does not reduce the current surge if the input power is interrupted for a short period of time not allowing the thermistor to cool down. Thermistors are fitted as standard to all mains input models except for 1-phase input of models > 2.5kW. Thermistors are available up to 45A. For higher input current an electronic inrush current limitation can be offered.
Option “ie” electronic inrush current limiting An electronic circuit limits the inrush current.
Option “sd” (series diode): A series diode protects the module against input voltage of wrong polarity (additional power losses).
Option “ad” (anti-parallel diode): To avoid the power losses of a series diode a diode is provided with opposite polarity in parallel to the input blowing an internal or external fuse if the module is connected to a supply with wrong polarity.
Option “au” (auto-ranging) For standard dual AC input models the range of 115/230Vac is to be selected by connecting the input line to different pins on the connector. With auto-ranging the unit senses the input voltage and provides automatically the correct connection.
Option “p” (power fail): A signal (logic or relay) is given if the input voltage (AC or DC) drops below the specified limit. In AC input units we sense the rectified input voltage so that a power fail alarm will not be triggered if at light loads mains power returns before the input capacitors are substantially discharged.
Option “r” (relay): A relay instead of a logic signal is provided for failure indication.
output options
Option “dd” (decoupling diode): For redundant operation the outputs of two or more units are paralleled behind de-coupling diodes so that an internal fault of one module does not affect the operation of the others. These diodes cause power losses.
Option “cs” (active current sharing): An additional control circuit provides active current sharing via an interconnecting wire between converters that operate in parallel. Active current sharing should be used for multi-output units operating in parallel.
Option “csi” (current sharing interrupt): Option "csi" will effect the removal of the "cs" signal. Should there be an instance where a unit is not supplying the load, then the effect of its "cs" signal is removed, and the load voltage is unaffected by this condition.
Option “h1” (inhibit): A terminal connected to the negative input line also shuts off the converter. This can also be used in conjunction with a thermal trip which shuts the unit down.
Option “h2” (inhibit): Operation of the unit is inhibited if a voltage signal (5V/10mA) is applied in reference to the negative line of the (main) output.
Option “rco” (reducing current limiting at over temperature) A circuit reduces the current limiting level at higher temperature (to be specified).
Option “d” (DC-ok, one output): A logic signal is given if the output voltage (main output in multi-output systems) is below the specified limit.
Option “m” (DC-ok, all outputs): In multi-output systems a logic signal is provided if the voltage of any output is below the specified limit.
Option “ac” (AC ok) A logic signal connected to relay contacts is given if the output voltage of an inverter is below the specified limit.
Option "y" (sys-reset): This logic signal is a combination of power fail and DC-ok as specified for VME systems.
Option "r" (relay): A relay instead of a logic signal is provided for failure indication.
environment options
Option "t" (tropical protection):The unit is given additional protection by a heavy coat of varnish on the printed circuit board(s) and components.
Option "c" (extended temperature range):The circuit is designed and tested for operation at an ambient temperature as low as –40 °C.
Option "ms" (increased mechanical strength): Screws are secured by Locktite and heavy components are fastened by ties and/or glue. Modules with the "ms" option meet the standard EN61373 regarding shock and vibration.
mechanical options
Standard mounting "Eurocassette" pluggable module for 19" sub-racks 8
Option "w" (wall mounting): Module is screwed against a mounting plate for installation in a cabinet. The load connections are typically a terminal block.
Option "cha" (chassis mount) Module is designed for installation to a structure or within cabinet. Screw type connectors are supplied with the module.
Option "din" (DIN rail mount) Module is designed for DIN rail mounting to a structure or within Cabinet. Screw type connectors are supplied with the module.
Schaefer_cb3500-AC-DC-PS-BatteryChargers-DC-DC-Converters.pdf

Find the Right Model

Model Number Input Voltage (Vdc) Output Voltage (Vdc) Output Current (A)
product variant C3520 18...36Vdc 5Vdc (Adj. 4.5 - 5.5Vdc) 80A
product variant C3521 18...36Vdc 9Vdc (Adj. 8 - 10Vdc) 55A
product variant C3522 18...36Vdc 12Vdc (Adj. 11 - 13Vdc) 50A
product variant C3523 18...36Vdc 15Vdc (Adj. 14 - 16Vdc) 40A
product variant C3524 18...36Vdc 24Vdc (Adj. 23 - 26Vdc) 27A
product variant C3525 18...36Vdc 28Vdc (Adj. 26 - 30Vdc) 23A
product variant C3529 18...36Vdc 48Vdc (Adj. 45 - 55Vdc) 12A
product variant C3526 18...36Vdc 60Vdc (Adj. 58 - 68Vdc) 10A
product variant C3527 18...36Vdc 110Vdc (Adj. 100 - 130Vdc) 5.3A
product variant C3527J 18...36Vdc 200Vdc (Adj. 190 - 200Vdc) 3.5A
product variant C3528 18...36Vdc 220Vdc (Adj. 200 - 250Vdc) 2.8A
product variant C3528J 18...36Vdc 400Vdc (Adj. 380 - 400Vdc) 1.7A
product variant C3530 36...75Vdc 5Vdc (Adj. 4.5 - 5.5Vdc) 100A
product variant C3531 36...75Vdc 9Vdc (Adj. 8 - 10Vdc) 65A
product variant C3532 36...75Vdc 12Vdc (Adj. 11 - 13Vdc) 56A
product variant C3533 36...75Vdc 15Vdc (Adj. 14 - 16Vdc) 45A
product variant C3534 36...75Vdc 24Vdc (Adj. 23 - 26Vdc) 30A
product variant C3535 36...75Vdc 28Vdc (Adj. 26 - 30Vdc) 27A
product variant C3539 36...75Vdc 48Vdc (Adj. 45 - 55Vdc) 14A
product variant C3536 36...75Vdc 60Vdc (Adj. 58 - 68Vdc) 12A
product variant C3537 36...75Vdc 110Vdc (Adj. 100 - 130Vdc) 6.5A
product variant C3537J 36...75Vdc 200Vdc (Adj. 190 - 200Vdc) 4A
product variant C3538 36...75Vdc 220Vdc (Adj. 200 - 250Vdc) 3.5A
product variant C3538J 36...75Vdc 400Vdc (Adj. 380 - 400Vdc) 2A
product variant C3540 45...90Vdc 5Vdc (Adj. 4.5 - 5.5Vdc) 100A
product variant C3541 45...90Vdc 9Vdc (Adj. 8 - 10Vdc) 65A
product variant C3542 45...90Vdc 12Vdc (Adj. 11 - 13Vdc) 56A
product variant C3543 45...90Vdc 15Vdc (Adj. 14 - 16Vdc) 45A
product variant C3544 45...90Vdc 24Vdc (Adj. 23 - 26Vdc) 30A
product variant C3545 45...90Vdc 28Vdc (Adj. 26 - 30Vdc) 27A
product variant C3549 45...90Vdc 48Vdc (Adj. 45 - 55Vdc) 14A
product variant C3546 45...90Vdc 60Vdc (Adj. 58 - 68Vdc) 12A
product variant C3547 45...90Vdc 110Vdc (Adj. 100 - 130Vdc) 6.5A
product variant C3547J 45...90Vdc 200Vdc (Adj. 190 - 200Vdc) 4A
product variant C3548 45...90Vdc 220Vdc (Adj. 200 - 250Vdc) 3.5A
product variant C3548J 45...90Vdc 400Vdc (Adj. 380 - 400Vdc) 2A
product variant C3550 80...160Vdc 5Vdc (Adj. 4.5 - 5.5Vdc) 100A
product variant C3551 80...160Vdc 9Vdc (Adj. 8 - 10Vdc) 65A
product variant C3552 80...160Vdc 12Vdc (Adj. 11 - 13Vdc) 56A
product variant C3553 80...160Vdc 15Vdc (Adj. 14 - 16Vdc) 45A
product variant C3554 80...160Vdc 24Vdc (Adj. 23 - 26Vdc) 30A
product variant C3555 80...160Vdc 28Vdc (Adj. 26 - 30Vdc) 27A
product variant C3559 80...160Vdc 48Vdc (Adj. 45 - 55Vdc) 14A
product variant C3556 80...160Vdc 60Vdc (Adj. 58 - 68Vdc) 12A
product variant C3557 80...160Vdc 110Vdc (Adj. 100 - 130Vdc) 6.5A
product variant C3557J 80...160Vdc 200Vdc (Adj. 190 - 200Vdc) 4A
product variant C3588 80...160Vdc 220Vdc (Adj. 200 - 250Vdc) 3.5A
product variant C3558J 80...160Vdc 400Vdc (Adj. 380 - 400Vdc) 2A
product variant C3570 160...320Vdc 5Vdc (Adj. 4.5 - 5.5Vdc) 100A
product variant C3571 160...320Vdc 9Vdc (Adj. 8 - 10Vdc) 65A
product variant C3572 160...320Vdc 12Vdc (Adj. 11 - 13Vdc) 56A
product variant C3573 160...320Vdc 15Vdc (Adj. 14 - 16Vdc) 45A
product variant C3574 160...320Vdc 24Vdc (Adj. 23 - 26Vdc) 30A
product variant C3575 160...320Vdc 28Vdc (Adj. 26 - 30Vdc) 27A
product variant C3579 160...320Vdc 48Vdc (Adj. 45 - 55Vdc) 14A
product variant C3576 160...320Vdc 60Vdc (Adj. 58 - 68Vdc) 12A
product variant C3577 160...320Vdc 110Vdc (Adj. 100 - 130Vdc) 6.5A
product variant C3577J 160...320Vdc 200Vdc (Adj. 190 - 200Vdc) 4A
product variant C3578 160...320Vdc 220Vdc (Adj. 200 - 250Vdc) 3.5A
product variant C3578J 160...320Vdc 400Vdc (Adj. 380 - 400Vdc) 2A
product variant C3580Z 320...380Vdc 5Vdc (Adj. 4.5 - 5.5Vdc) 100A
product variant C3581Z 320...380Vdc 9Vdc (Adj. 8 - 10Vdc) 65A
product variant C3582Z 320...380Vdc 12Vdc (Adj. 11 - 13Vdc) 56A
product variant C3583Z 320...380Vdc 15Vdc (Adj. 14 - 16Vdc) 45A
product variant C3584Z 320...380Vdc 24Vdc (Adj. 23 - 26Vdc) 30A
product variant C3585Z 320...380Vdc 28Vdc (Adj. 26 - 30Vdc) 27A
product variant C3589Z 320...380Vdc 48Vdc (Adj. 45 - 55Vdc) 14A
product variant C3586Z 320...380Vdc 60Vdc (Adj. 58 - 68Vdc) 12A
product variant C3587Z 320...380Vdc 110Vdc (Adj. 100 - 130Vdc) 6.5A
product variant C3587ZJ 320...380Vdc 200Vdc (Adj. 190 - 200Vdc) 4A
product variant C3588Z 320...380Vdc 220Vdc (Adj. 200 - 250Vdc) 3.5A
product variant C3588ZJ 320...380Vdc 400Vdc (Adj. 380 - 400Vdc) 2A
product variant C3570G 320...640Vdc 5Vdc (Adj. 4.5 - 5.5Vdc) 100A
product variant C3571G 320...640Vdc 9Vdc (Adj. 8 - 10Vdc) 65A
product variant C3572G 320...640Vdc 12Vdc (Adj. 11 - 13Vdc) 56A
product variant C3573G 320...640Vdc 15Vdc (Adj. 14 - 16Vdc) 45A
product variant C3574G 320...640Vdc 24Vdc (Adj. 23 - 26Vdc) 30A
product variant C3575G 320...640Vdc 28Vdc (Adj. 26 - 30Vdc) 27A
product variant C3579G 320...640Vdc 48Vdc (Adj. 45 - 55Vdc) 14A
product variant C3576G 320...640Vdc 60Vdc (Adj. 58 - 68Vdc) 12A
product variant C3577G 320...640Vdc 110Vdc (Adj. 100 - 130Vdc) 6.5A
product variant C3577GJ 320...640Vdc 200Vdc (Adj. 190 - 200Vdc) 4A
product variant C3578G 320...640Vdc 220Vdc (Adj. 200 - 250Vdc) 3.5A
product variant C3578GJ 320...640Vdc 400Vdc (Adj. 380 - 400Vdc) 2A

Need help finding the right product model?