DC/DC Converters
Polyamp PSC 600 SERIES DC/DC Converter
The Polyamp PSC600 Series DC/DC Converter is a high-performance solution for industrial, railway, and telecommunications applications. Designed to deliver reliable power, it offers robust functionality and flexibility in demanding environments.
Read MoreFeatures
- 250W - 800W Industrial Converter
- Optimised input voltage ranges
- Input ranges from 24 to 440Vdc
- Single outputs from 5 to 125Vdc
- Reverse input voltage protection
- Conformal coating - tropic
Specifications
Selection Table
Technical Illustrations
Downloads
INPUT | |
---|---|
Input voltage | 24V, 48V, 110V, 220V See Selection Table for details |
Reverse input voltage protection | Parallel diode (Input code: 24, 48) Series diode (Input code: 110, 220) |
output | |
---|---|
Output Voltage | See Selection Table |
Output Current | See Selection Table |
Source regulation | 0.2%. |
Load regulation | 0.2%. |
Output ripple (50kHz) | Typ. 20mV p-p typ. |
Input ripple attenuation | 150:1 On output 50 to 400Hz |
Voltage adjustment | 90% - 110%. |
Current limit protection | 105%. Rectangular |
Overvoltage protection | 115%. |
Under voltage alarm | 90% of nominal output. |
Remote sense | Option S. |
Soft start | Yes. |
Start-up time1s | |
Hold-up time | 2-25ms |
Efficiency | 80 - 93% |
Switching frequency | 50 kHz |
OPERATING | |
---|---|
Efficiency | 80%–93% |
Design topology | Push-pull / Full-Bridge |
Switching frequency | 50kH |
Overvoltage protection | Yes, 115% of nominal voltage |
Isolation | Input / Output: 2.5kVac, 4kVdc Input / Case: 4kVdc Output / Case: 2kVdc, all outputs |
ENVIRONMENTAL | |
---|---|
Operating temperature | -25°C to 70°C (100% load, single output >10Vdc). -25°C to +55°C (100% load, single output <10Vdc). |
Temperature coefficient | 0.02%/°C. |
Cooling | Convectional cooling. |
Storage temperature | -40°C to 85°C. |
FEATURES | |
---|---|
Overvoltage protection OVP | The output voltage is limited to 15% over nominal output voltage by a extra regulated circuit |
Under voltage alarm | A built in alarm changes to alarm state if the converter output voltage drops 10% below nominal output. The DC OK LED is also controlled by the alarm circuit. The alarm has a relay output with both [NO] and [NC] function. The relay rating is 30V 1A(ac & dc) |
Reverse input voltage Protection | On input code 24 and 48 the reverse voltage protection is provided by a parallel diode. This diode is only intended to blow and external input fuse. On input code 110 and 220, the reverse voltage protection is provided by a series diode. The converter will never start. |
Inrush current limit | On input code 110 and 220 the inrush limit circuit is always active thus acting at voltage dips below the stop level >10ms. On input code 24 and 48 this function is optional. |
Adjustment & measurement | Output voltage adjust potentiometer and output voltage measurement points are accessible from the front panel. |
Conformal Coating | the PSC series is conformally coated to withstand non-condensing tropical environment. |
OPTIONAL FEATURES | |
---|---|
Wider input range | The PSC600 series can be supplied with wide inptu range to meet train or mobile applications demands |
Built in series diode - C | Series diode on the output, which is mounted inside the case. Use this option when the output is connected in parallel with other power supply to achieve redundancy |
Built in series diode with resistor - CR | The CR option automatically balance the load between 2 or more paralleled PSC600 units. Used in hotswap. |
Remote Sense - S | The voltage sensing can be put at the load to compensate for voltage drop. The sense circuit is a standard feature on 5V outputs. |
Inrush Current LImit | On input code 24 and 48 the inrush limit circuit is optional. This option affects the input voltage range. The circuit is always active thus acting at voltage dips below the stop level > 10ms. |
Higher insulation on output - E2 | Output/case 2.5kVAC for 12 to 125Vdc |
Over current shutdown - OCSD | The PSC600 series can provide over current during a limited time. The OCSD circuit shut down the unit when a preset time has passed. This delay can be pre-set between 100ms to 3 seconds. |
STANDARDS | |
---|---|
Safety | IEC60950 |
EMC | EN 61000-6-3, Emission EN61000-6-2, Immunity EN IEC 61000-4-4, 4kV EN IEC 61000-4-5 level 2 & 3 |
C-Tick | AS/NZS CISPR11: 2002 Group1 Class A |
MECHANICAL | |
---|---|
Dimensions | See Technical Illustrations |
Weight | Base mechanic unit; 3.3Kg Base mechanic unit + 1 extra heatsink 4.0kg Base mechanic unit + 2 extra heatsinks 4.7kg |
MODEL NUMBER | INPUT | OUTPUT | CURRENT | OUTPUT POWER |
---|---|---|---|---|
PSC250 24/5 | 20-32V | 5V | 50A | 250W |
PSC400 24/12 | 20-32V | 12V | 33A | 400W |
PSC400 24/15 | 20-32V | 15V | 27A | 400W |
PSC600 24/24 | 20-32V | 24V | 25A | 600W |
PSC600 24/48 | 20-32V | 48V | 12.5A | 600W |
PSC600 24/110 | 20-32V | 110V | 5.5A | 600W |
PSC600 24/125 | 20-32V | 125V | 4.8A | 600W |
PSC250 48/5 | 41-60V | 5V | 50A | 250W |
PSC400 48/12 | 41-60V | 12V | 33A | 400W |
PSC700 48/12 | 41-60V | 12V | 60A | 720W |
PSC400 48/15 | 41-60V | 15V | 27A | 400W |
PSC800 48/15 | 41-60V | 15V | 54A | 800W |
PSC600 48/24 | 41-60V | 24V | 25A | 600W |
PSC800 48/24 | 41-60V | 24V | 33A | 800W |
PSC600 48/48 | 41-60V | 48V | 12.5A | 600W |
PSC800 48/48 | 41-60V | 48V | 17A | 800W |
PSC600 48/110 | 41-60V | 110V | 5.5A | 600W |
PSC800 48/110 | 41-60V | 110V | 7.3A | 800W |
PSC600 48/125 | 41-60V | 125V | 4.8A | 600W |
PSC800 48/125 | 41-60V | 125V | 6.4A | 800W |
PSC250 110/5 | 93-150V | 5V | 50A | 250W |
PSC400 110/12 | 93-150V | 12V | 33A | 400W |
PSC700 110/12 | 93-150V | 12V | 60A | 720W |
PSC400 110/15 | 93-150V | 15V | 27A | 400W |
PSC800 110/15 | 93-150V | 15V | 54A | 800W |
PSC600 110/24 | 93-150V | 24V | 25A | 600W |
PSC800 110/24 | 93-150V | 24V | 33A | 800W |
PSC600 110/48 | 93-150V | 48V | 12.5A | 600W |
PSC800 110/48 | 93-150V | 48V | 17A | 800W |
PSC600 110/110 | 93-150V | 110V | 5.5A | 600W |
PSC800 110/110 | 93-150V | 110V | 7.3A | 800W |
PSC600 110/125 | 93-150V | 125V | 4.8A | 600W |
PSC800 110/125 | 93-150V | 125V | 6.4A | 800W |
PSC250 220/5 | 187-300V | 5V | 50A | 250W |
PSC400 220/12 | 187-300V | 12V | 33A | 400W |
PSC700 220/12 | 187-300V | 12V | 60A | 720W |
PSC400 220/15 | 187-300V | 15V | 27A | 400W |
PSC800 220/15 | 187-300V | 15V | 54A | 800W |
PSC600 220/24 | 187-300V | 24V | 25A | 600W |
PSC800 220/24 | 187-300V | 24V | 33A | 800W |
PSC600 220/48 | 187-300V | 48V | 12.5A | 600W |
PSC800 220/48 | 187-300V | 48V | 17A | 800W |
PSC600 220/110 | 187-300V | 110V | 5.5A | 600W |
PSC800 220/110 | 187-300V | 110V | 7.3A | 800W |
PSC600 220/125 | 187-300V | 125V | 4.8A | 600W |
PSC800 220/125 | 187-300V | 125V | 6.4A | 800W |

INPUT | |
---|---|
Input voltage | 24V, 48V, 110V, 220V See Selection Table for details |
Reverse input voltage protection | Parallel diode (Input code: 24, 48) Series diode (Input code: 110, 220) |
output | |
---|---|
Output Voltage | See Selection Table |
Output Current | See Selection Table |
Source regulation | 0.2%. |
Load regulation | 0.2%. |
Output ripple (50kHz) | Typ. 20mV p-p typ. |
Input ripple attenuation | 150:1 On output 50 to 400Hz |
Voltage adjustment | 90% - 110%. |
Current limit protection | 105%. Rectangular |
Overvoltage protection | 115%. |
Under voltage alarm | 90% of nominal output. |
Remote sense | Option S. |
Soft start | Yes. |
Start-up time1s | |
Hold-up time | 2-25ms |
Efficiency | 80 - 93% |
Switching frequency | 50 kHz |
OPERATING | |
---|---|
Efficiency | 80%–93% |
Design topology | Push-pull / Full-Bridge |
Switching frequency | 50kH |
Overvoltage protection | Yes, 115% of nominal voltage |
Isolation | Input / Output: 2.5kVac, 4kVdc Input / Case: 4kVdc Output / Case: 2kVdc, all outputs |
ENVIRONMENTAL | |
---|---|
Operating temperature | -25°C to 70°C (100% load, single output >10Vdc). -25°C to +55°C (100% load, single output <10Vdc). |
Temperature coefficient | 0.02%/°C. |
Cooling | Convectional cooling. |
Storage temperature | -40°C to 85°C. |
FEATURES | |
---|---|
Overvoltage protection OVP | The output voltage is limited to 15% over nominal output voltage by a extra regulated circuit |
Under voltage alarm | A built in alarm changes to alarm state if the converter output voltage drops 10% below nominal output. The DC OK LED is also controlled by the alarm circuit. The alarm has a relay output with both [NO] and [NC] function. The relay rating is 30V 1A(ac & dc) |
Reverse input voltage Protection | On input code 24 and 48 the reverse voltage protection is provided by a parallel diode. This diode is only intended to blow and external input fuse. On input code 110 and 220, the reverse voltage protection is provided by a series diode. The converter will never start. |
Inrush current limit | On input code 110 and 220 the inrush limit circuit is always active thus acting at voltage dips below the stop level >10ms. On input code 24 and 48 this function is optional. |
Adjustment & measurement | Output voltage adjust potentiometer and output voltage measurement points are accessible from the front panel. |
Conformal Coating | the PSC series is conformally coated to withstand non-condensing tropical environment. |
OPTIONAL FEATURES | |
---|---|
Wider input range | The PSC600 series can be supplied with wide inptu range to meet train or mobile applications demands |
Built in series diode - C | Series diode on the output, which is mounted inside the case. Use this option when the output is connected in parallel with other power supply to achieve redundancy |
Built in series diode with resistor - CR | The CR option automatically balance the load between 2 or more paralleled PSC600 units. Used in hotswap. |
Remote Sense - S | The voltage sensing can be put at the load to compensate for voltage drop. The sense circuit is a standard feature on 5V outputs. |
Inrush Current LImit | On input code 24 and 48 the inrush limit circuit is optional. This option affects the input voltage range. The circuit is always active thus acting at voltage dips below the stop level > 10ms. |
Higher insulation on output - E2 | Output/case 2.5kVAC for 12 to 125Vdc |
Over current shutdown - OCSD | The PSC600 series can provide over current during a limited time. The OCSD circuit shut down the unit when a preset time has passed. This delay can be pre-set between 100ms to 3 seconds. |
STANDARDS | |
---|---|
Safety | IEC60950 |
EMC | EN 61000-6-3, Emission EN61000-6-2, Immunity EN IEC 61000-4-4, 4kV EN IEC 61000-4-5 level 2 & 3 |
C-Tick | AS/NZS CISPR11: 2002 Group1 Class A |
MECHANICAL | |
---|---|
Dimensions | See Technical Illustrations |
Weight | Base mechanic unit; 3.3Kg Base mechanic unit + 1 extra heatsink 4.0kg Base mechanic unit + 2 extra heatsinks 4.7kg |
MODEL NUMBER | INPUT | OUTPUT | CURRENT | OUTPUT POWER |
---|---|---|---|---|
PSC250 24/5 | 20-32V | 5V | 50A | 250W |
PSC400 24/12 | 20-32V | 12V | 33A | 400W |
PSC400 24/15 | 20-32V | 15V | 27A | 400W |
PSC600 24/24 | 20-32V | 24V | 25A | 600W |
PSC600 24/48 | 20-32V | 48V | 12.5A | 600W |
PSC600 24/110 | 20-32V | 110V | 5.5A | 600W |
PSC600 24/125 | 20-32V | 125V | 4.8A | 600W |
PSC250 48/5 | 41-60V | 5V | 50A | 250W |
PSC400 48/12 | 41-60V | 12V | 33A | 400W |
PSC700 48/12 | 41-60V | 12V | 60A | 720W |
PSC400 48/15 | 41-60V | 15V | 27A | 400W |
PSC800 48/15 | 41-60V | 15V | 54A | 800W |
PSC600 48/24 | 41-60V | 24V | 25A | 600W |
PSC800 48/24 | 41-60V | 24V | 33A | 800W |
PSC600 48/48 | 41-60V | 48V | 12.5A | 600W |
PSC800 48/48 | 41-60V | 48V | 17A | 800W |
PSC600 48/110 | 41-60V | 110V | 5.5A | 600W |
PSC800 48/110 | 41-60V | 110V | 7.3A | 800W |
PSC600 48/125 | 41-60V | 125V | 4.8A | 600W |
PSC800 48/125 | 41-60V | 125V | 6.4A | 800W |
PSC250 110/5 | 93-150V | 5V | 50A | 250W |
PSC400 110/12 | 93-150V | 12V | 33A | 400W |
PSC700 110/12 | 93-150V | 12V | 60A | 720W |
PSC400 110/15 | 93-150V | 15V | 27A | 400W |
PSC800 110/15 | 93-150V | 15V | 54A | 800W |
PSC600 110/24 | 93-150V | 24V | 25A | 600W |
PSC800 110/24 | 93-150V | 24V | 33A | 800W |
PSC600 110/48 | 93-150V | 48V | 12.5A | 600W |
PSC800 110/48 | 93-150V | 48V | 17A | 800W |
PSC600 110/110 | 93-150V | 110V | 5.5A | 600W |
PSC800 110/110 | 93-150V | 110V | 7.3A | 800W |
PSC600 110/125 | 93-150V | 125V | 4.8A | 600W |
PSC800 110/125 | 93-150V | 125V | 6.4A | 800W |
PSC250 220/5 | 187-300V | 5V | 50A | 250W |
PSC400 220/12 | 187-300V | 12V | 33A | 400W |
PSC700 220/12 | 187-300V | 12V | 60A | 720W |
PSC400 220/15 | 187-300V | 15V | 27A | 400W |
PSC800 220/15 | 187-300V | 15V | 54A | 800W |
PSC600 220/24 | 187-300V | 24V | 25A | 600W |
PSC800 220/24 | 187-300V | 24V | 33A | 800W |
PSC600 220/48 | 187-300V | 48V | 12.5A | 600W |
PSC800 220/48 | 187-300V | 48V | 17A | 800W |
PSC600 220/110 | 187-300V | 110V | 5.5A | 600W |
PSC800 220/110 | 187-300V | 110V | 7.3A | 800W |
PSC600 220/125 | 187-300V | 125V | 4.8A | 600W |
PSC800 220/125 | 187-300V | 125V | 6.4A | 800W |

Find the Right Model
Model Number | Input Voltage (Vdc) | Output Voltage (Vdc) | Output Current (A) | ||
---|---|---|---|---|---|
![]() |
PSC400 24T/13.2 | 24Vdc: 16...34Vdc | 13.2Vdc | 30A | |
![]() |
PSC400 24T/15 | 24Vdc: 16...34Vdc | 15Vdc | 27A | |
![]() |
PSC500 24T/24 | 24Vdc: 16...34Vdc | 24Vdc | 21A | |
![]() |
PSC600 24T/24 | 24Vdc: 16...34Vdc | 24Vdc | 25A | |
![]() |
PSC600 24T/48 | 24Vdc: 16...34Vdc | 48Vdc | 13A | |
![]() |
PSC500 24/13.2 | 24Vdc: 18...32Vdc | 13.2Vdc | 38A | |
![]() |
PSC500 24/15 | 24Vdc: 18...32Vdc | 15Vdc | 33A | |
![]() |
PSC600 24/28 | 24Vdc: 18...32Vdc | 28Vdc | 21A | |
![]() |
PSC600 24/53 | 24Vdc: 18...32Vdc | 53Vdc | 11A | |
![]() |
PSC600 24/110 | 24Vdc: 18...32Vdc | 110Vdc | 5.5A | |
![]() |
PSC600 24/125 | 24Vdc: 18...32Vdc | 125Vdc | 4.8A | |
![]() |
PSC400 48/12 | 48Vdc: 38...60Vdc | 12Vdc | 17.5A | |
![]() |
PSC400 48/13.2 | 48Vdc: 38...60Vdc | 13.2Vdc | 12.5A | |
![]() |
PSC400 48/15 | 48Vdc: 38...60Vdc | 15Vdc | 14A | |
![]() |
PSC600 48/24 | 48Vdc: 38...60Vdc | 24Vdc | 25A | |
![]() |
PSC600 48/48 | 48Vdc: 38...60Vdc | 48Vdc | 12.5A | |
![]() |
PSC600 48/110 | 48Vdc: 38...60Vdc | 110Vdc | 5.5A | |
![]() |
PSC400 110/12 | 110Vdc: 88...150Vdc | 12Vdc | 17.5A | |
![]() |
PSC400 110/13.2 | 110Vdc: 88...150Vdc | 13.2Vdc | 12.5A | |
![]() |
PSC400 110/15 | 110Vdc: 88...150Vdc | 15Vdc | 14A | |
![]() |
PSC600 110/24 | 110Vdc: 88...150Vdc | 24Vdc | 25A | |
![]() |
PSC600 110/48 | 110Vdc: 88...150Vdc | 48Vdc | 12.5A | |
![]() |
PSC600 110/110 | 110Vdc: 88...150Vdc | 110Vdc | 5.5A | |
![]() |
PSC600 110/220 | 110Vdc: 88...150Vdc | 220Vdc | 2.7A | |
![]() |
PSC400 220/12 | 400Vdc: 175...300Vdc | 12Vdc | 17.5A | |
![]() |
PSC400 220/13.2 | 400Vdc: 175...300Vdc | 13.2Vdc | 12.5A | |
![]() |
PSC400 220/15 | 400Vdc: 175...300Vdc | 15Vdc | 14A | |
![]() |
PSC600 220/24 | 400Vdc: 175...300Vdc | 24Vdc | 25A | |
![]() |
PSC600 220/48 | 400Vdc: 175...300Vdc | 48Vdc | 12.5A | |
![]() |
PSC600 220/110 | 400Vdc: 175...300Vdc | 110Vdc | 5.5A | |
![]() |
PSC600 220/220 | 400Vdc: 175...300Vdc | 220Vdc | 2.7A | |
![]() |
PSC400 440/13.2 | 400Vdc: 350...550Vdc | 13.2Vdc | 12.5A | |
![]() |
PSC600 440/24 | 400Vdc: 350...550Vdc | 24Vdc | 25A | |
![]() |
PSC600 440/48 | 400Vdc: 350...550Vdc | 48Vdc | 12.5A | |
![]() |
PSC600 440/110 | 400Vdc: 350...550Vdc | 110Vdc | 5.5A | |
![]() |
PSC600 440/220 | 400Vdc: 350...550Vdc | 220Vdc | 2.7A |
Need help finding the right product model?