Product Quick Selection Wheel

180... 280W SINGLE OUTPUT DC/DC CONVERTERS PREMIUM CRS-240 SERIES

Features
  • High input-output isolation
  • Adjustable output voltage
  • Remote sensing
  • Input voltage OK LED
  • Output voltage presence LED
  • Remote inhibit
  • Efficiency up to 92%
  • Universal mounting via DIN - Wall - Chassis

PREMIUM CRS-240 SERIES

Product Overview

The CRS-240 series consists of DC-DC converters, with a galvanic isolation between input and output. The converters operate at a fixed switching frequency and use push-pull converter topology.

For maximum regulation, the remote sensing terminals can be connected to the load. This will allow a power cable voltage drop of up to 0.3 V on each cable to be offset. The device is protected against overload and short-circuits by means of a current limiting circuit.

The device is also protected against reverse polarity input voltage, and the input fuse blows if an improper connection is made.

When a converter input undervoltage condition occurs, the converter is disabled, thus preventing the battery from becoming totally discharged.

Specifications

INPUT
Voltage See table
Undervoltage shutdown 55% to 60% Vi nom
Max allowed input ripple 15% Vin nom (EN50155)
OUTPUT
Output Voltage See selection table.

Voltage Adjustment

-10% ... +15% Vo nom

Line regulation (Io = nom)

< 0,2 % (Io = nom)

Load regulation (Vin = nom)

< 0,2 % (Vin = nom; Io: 0...100%)

Ripple

< 50 mVpp

Noise (BW = 20MHz)

< 100 mVpp

 

 
ENVIRONMENTAL

StorageTemperature

-40°C ... 85°C

Operating temperature range at Io= 100% -25°C ... 60°C (-40°C ... 60°C see note-1 below)
Operating temperature range at Io= 50% -25°C ... 80°C (-40°C ... 80°C, see note-1)
Maximum Relative humidity 95% with no condensation
MTBF 400.000h @ 40°C according to IEC61709
EMC

Emission

EN61000-6-3

Immunity

EN61000-6-2

SAFETY

Safety

EN60950-1, EN62368-1

Dielectric strength Input-Output

3000Vac, 4200Vdc 1min.

Dielectric strength Input-GND

1500Vac, 2100Vdc 1min.

Dielectric strength Output-GND

1500Vac, 2100Vdc 1min.

MECHANICAL

Approximate weight

640g

Dimensions

100 x 220 x 38.5mm

CONTROL

Remote inhibit range

5V ... 24V

Remote sense

< 0.3V per pole

PROTECTIONS

Against overloads and short-circuits

Current limiting

Against reverse input voltage

Input fuse

Against input under-voltage

Under-voltage lock-out

Against Input over-currents

Input fuse

Note-1: The unit can start up and work at an ambient temperature of -40°C with the following restrictions:

- Do not handle the connection terminals below -25°C

- The output ripple can rise up to 150mVpp at -40°C

Selection Table

 

 

PART NUMBER

POWER (W)

INPUT (V)

INPUT RANGE (V)

OUTPUT (V)OUTPUT CURRENT (A)EFFICIENCY(%)
CRS-240-6351 180 12 9- 15 5 36 79
CRS-240-6352 180 12 9 - 15 12 15 80
CRS-240-6353 200 12 9 - 15 24 8,33 82
CRS-240-6354 200 12 9 - 15 48 4,17 82
CRS-240-6355 180 24 18 - 30 5 36 80
CRS-240-6356 240 24 18 - 30 12 20 83
CRS-240-6357 240 24 18 - 30 24 10 87
CRS-240-6358 240 24 18 - 30 48 5 88
CRS-240-6359 180 48 36 - 72 5 36 80
CRS-240-6360 240 48 36 - 72 12 20 84
CRS-240-6361 280 48 36 - 72 24 11,7 88
CRS-240-6362 280 48 36 - 72 48 5,8 89
CRS-240-6363 180 72 50,4 - 90 5 36 81
CRS-240-6364 240 72 50,4 - 90 12 20 88
CRS-240-6365 280 72 50,4 - 90 24 11,7 90
CRS-240-6366 280 72 50,4 - 90 48 5,8 90
CRS-240-6367 180 110 77 - 144 5 36 81
CRS-240-6368 240 110 77 - 144 12 20 88
CRS-240-6369 280 110 77 - 144 24 11,7 91
CRS-240-6370 280 110 77 - 144 48 5,8 92
CRS-240-6371 180 220 165 - 275 5 36 81
CRS-240-6372 240 220 165 - 275 12 20 88
CRS-240-6373 280 220 165 - 275 24  11,7 91
CRS-240-6374 280 220 165 - 275 48  5,8 92

Technical Illustration

  • Dimensions Dimensions
  • Blocks Diagram Blocks Diagram
  • Connections Connections
  • Typical Output Characteristic Typical Output Characteristic
  • Power Derating vs. Ambient Temp. Power Derating vs. Ambient Temp.
  • Accessories Accessories